Vista de pagina 94
16-1
SECTION 16
Event Log Options
•••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
General Information
Event Log Printer Connections
Programming Event Log Options
Event Logging Procedures
•••••••••••••••••••••••••••••••••••••••••••••••••
General Information
This system has the ability to record up to 224 events of various types in a history log. Each
event is recorded in one of six categories with the time and date of its occurrence (if real-time
clock is set). These categories are:
Alarm
Supervisory/check
Bypass
Open/close
System conditions
Test
The log may be viewed (Display Mode) on an alpha keypad, or can be printed (Print Mode) on
a serial printer (connected to the system via a 4100SM Serial Interface Module).
Event Log Printer Connections
The VISTA-128B's event log can be printed on a local serial printer.
Connect a UL EDP Listed serial printer to the J7 connector using an ADEMCO 4100SM
Interface Module, as shown in