ADDENDUM: Battery Backup (continued)
3
Note: The cabinet supplied with the VISTA-128B panel can house up to 12V, 14AH batteries (two
12V, 7AH batteries wired in parallel). The VISTA-ULKT kit provides a cabinet that can house up to
12V, 17.2AH batteries and that may be used with this panel. The total standby current drawn from the
auxiliary power and polling loop outputs combined must be limited to 270mA when 14AH batteries are
used; and to 390mA when 17.2AH batteries are used.
Table 2: Total Current Drain Table
Source of Current Drain Total Standby Current Total Alarm Current
Auxiliary Power Output:
Polling Loop Output:
Bell Output: Not Applicable
PCB Current: 250mA 330mA
Total Current:
Table 3: Battery Calculation Table
Capacity Formula
Calculated Value
Standby
Capacity
For 4-hour standby time, use following formula:
Total standby load x 4 hours x 1.4 loading/contingency factor
For 24-hour standby time, use following formula:
Total standby load x 24 hours x 1.1 contingency factor
Alarm
Capacity
Total alarm load x 0.06 hours (for 4-minute
alarm)
x 0.25 hours (for 15-
minute alarm)
Total
Capacity
Add standby and alarm capacities
Table 4: Battery Selection Table
Capacity Recommended Battery Comments
4AH
Yuasa NP4-12
7AH Yuasa NP7-12
12AH Yuasa NP12-12 Fits in large mercantile cabinet only
14AH Yuasa NP7-12 Connect two in parallel
17.2AH Yuasa NPG18-12 Fits in large mercantile cabinet only