14-1
SECTION 14
Access Control
•••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
♦
General Information
♦
Access Control of an Entry/Exit Point
♦
Access Control Dialer Events
♦
Wiring the Vista Gateway Module
♦
Programming the Vista Gateway Module
•••••••••••••••••••••••••••••••••••••••••••••••••
U
L
Interfacing the VISTA-128B with the PassPoint Access Control System via the Vista Gateway
Module is not permissible for UL commercial burglary installations.
General Information
The VISTA-128B is capable of interacting with the ADEMCO PassPoint Access Control
System (PassPoint ACS). The VISTA-128B processes fire, burglary, arm, disarm and other
information. The PassPoint ACS processes card reader information and controls the locking
and unlocking of doors. The sharing of information between the two systems is provided by
the Vista Gateway Module, (VGM).
The VGM is connected between the ECP bus (keypad terminals) of the control and the
network bus of the PassPoint ACS (see
Figure 14-1
). The control sends the VGM its status
information, event log entries and entry/exit requests, (inputs programmed with response
type Access Point), from keypads, hardwired zones, and rf transmitters. The VGM then
reformats and retransmits this information to the Main Logic Board, (MLB) on the PassPoint
ACS network bus.
The VISTA-128B is able to control the following on the PassPoint ACS:
•
Access Points
The PassPoint ACS is able to control the following on the VISTA-128B:
•
Relays
•
Arming/disarming schedules
•
Keypad Display
•
Time/date synchronization of the two systems
See the documentation that comes with the PassPoint ACS for details
.
The PassPoint ACS can dedicate some of its inputs for use as regular VISTA-128B hardwired
zones (the zone response type is ACS). The PassPoint ACS can also utilize the VISTA-128B’s
dialer for reports to the central station.