Section 22 – Data Field Descriptions
22-3
*23 MULTIPLE ALARMS (partition-specific) [1]
Determines whether or not more than one alarm can be sounded in a given zone during
an armed period. Note that multiple alarm soundings will not occur more frequently
than allowed by the programmed alarm sounder duration. This selection applies to local
sounding and has no impact on the number of communication messages transmitted.
Refer to
84
Swinger Suppression for limiting communication messages. Enter 1 if this
feature is desired. Enter 0 if not desired. Must be 1 for UL installations.
*24 IGNORE EXPANSION ZONE TAMPER [0]
Enter 1 to disable (ignore) tamper.
Enter 0 if tamper detection is desired. Must be
0
for UL installations.
Note:
Only applicable to certain polling loop sensors with tamper switches or 5800
Series transmitters. This option is used to disable tamper detection on these devices.
*25 BURG. TRIGGER FOR RESPONSE TYPE 8 [1]
Enter 1 to allow optional triggering of the voltage output on Pin 3 of the J2 header to
include zone response type 8 (24-hr. auxiliary).
Enter 0 if only burglary and audible panic alarms (zone type 7) will trigger Pin 3.
*26 INTELLIGENT TEST REPORTING [0]
Enter
1
if no test report is to be sent if any other type of report was sent since the last
test report.
Enter
0
if test reports are to be sent at the set intervals, regardless of whether or not
other reports have been sent. Must be
0
for UL applications.
*27 TEST REPORT INTERVAL [024]
||
Enter the test reporting interval in hours,
001-999.
Enter
000
if no test reporting is desired. If a test report is desired, enter a test code in
Report Code Programming in the #93 Menu Mode.
Set first test report time in field *83.
Max. 024 for UL commercial burglary installations.
*28 POWER UP IN PREVIOUS STATE [1]
Enter
1
if upon power-up, after a prolonged power loss which caused the system's
battery to discharge, the system will assume the system status prior to the power loss.
Enter
0
if the system is always to power up in a disarmed state. When the system
powers up armed, an alarm will occur 3 minutes after arming if a zone is faulted. When
so armed, the system reports closing as User #0 if Open/Close reporting for installer was
enabled in field *39. Note that if the previous state was armed AWAY or STAY, the
system may not respond to sensor changes for a small period of time (1-3 min.), which
allows sensors such as PIRs to stabilize.
Note:
Must be
1
for UL applications. Note that authority levels 0 or 5 cannot be used to
disarm the system if the control powers up armed.
Vista de pagina 122