VISTA-128B Installation Instructions
5-4
4. After addresses are set, the green READY LED should light, and the words
“DISARMED...READY TO ARM” should be displayed on keypads set to addresses 00, and
01.
5. If the “READY” message does not appear on any of the keypads in the system (in either
of the partitions), or a “NOT READY” message is displayed, check the keypad wiring
connections. Make sure each of the 8 basic hardwired zones has a 2000-ohm resistor
connected across its terminals.
6. When the proper “READY” message is displayed on the keypad(s), the system is
functioning properly.
7. Do not remove the EOL resistors until you are ready to make connections to the
hardwired zones, to allow for testing described later in the manual.
If an “OC” or “OPEN CIRCUIT” message is present on the keypad, data from the control is not
reaching the keypad. Please check your wiring.