VISTA-128B Installation Instructions
23-22
SOUND OPTION
If device type 1 (alpha keypad) is entered, this prompt will
appear. Keypads can be individually programmed to suppress
arm/disarm beeps, entry/exit beeps and chime mode beeps. This
helps prevent unwanted sounds from disturbing users in other
areas of the premises.
Enter a number 00-03 for the keypad sounding suppression
options desired for the keypad as follows:
00 = no suppression.
01 = suppress arm/disarm & entry/exit beeps.
02 = suppress chime mode beeps only.
03 = suppress arm/disarm, entry/exit and chime mode
beeps.
Press [∗] to accept entry.
KEYPAD GLBL?
If device type 1 (alpha keypad) is entered, this prompt will
appear. Each keypad can give users with access to multiple
partitions the ability to arm and disarm those partitions from
it. To enable this keypad for global arming/disarming, enter 1.
To prevent the ability to use this keypad for global
arming/disarming, enter 0.
Press
[∗]
to accept entry.
RF Expander
RF EXPANDER
HOUSE ID XX
If device type 3 (RF receiver) is selected, this prompt will
appear. Enter the 2-digit House ID (00-31). This is required if
using a wireless keypad (5827/5827BD) with a 5800 Series
system.
Press [∗] to accept entry.
Output Relay Module
SUPERVISED CF?
If device type 4 (relay module) is selected, this prompt will
appear. Enter 1 if the unit is a 4204CF. If not, enter 0. If 1 is
entered, only Relay 1 (Output A) and Relay 3 (Output B) on
each module are able to be programmed for functions. This
module is usually used to add two additional supervised bell
outputs to the system.
Press [∗] to accept entry.