VISTA-128B Installation Instructions
7-2
Wiring/Addressing RPM Devices
All devices on the polling loop must be wired in parallel to the [+] and [-] polling loop
terminals of the control panel (24 and 25). You can wire from device to device, or have
multiple branches connected directly to the control panel in a star configuration as shown in
Figure 7-1.
Although each polling loop device is wired in parallel, each device has its own unique zone
number (or group of zones if it is a zone expansion device). On some devices, this is
determined by the setting of DIP switches. Other devices have a built-in unique serial
number which must be "learned" into the control as the zone number desired. Set up the
polling loop as follows:
1. Run wires to each device on the polling loop. No individual wire run may exceed the
lengths given in the table to follow. In addition, no more than 64mA may be drawn on
any individual wire run. When a star configuration is used, the total length of all wire
runs combined cannot exceed 4000 ft (2000 ft. if using unshielded wire in conduit or
shielded wire). Twisted-pair is recommended for all normal wire runs.
Maximum Polling Loop Wire Runs
Wire Gauge Max. Length
#22 gauge 650 feet
#20 gauge 950 feet
#18 gauge 1500 feet
#16 gauge 2400 feet
When running polling loop wires, they must not be run within 6" of AC power, telephone, or
intercom wiring. Since the polling loop is carrying data between the control panel and the
devices, interference on this loop can cause an interruption of this communication. The polling
loop can also cause outgoing interference on the intercom or phone lines. If this spacing cannot
be achieved, shielded wire must be used. (Note that the maximum total wire length supported is
cut in half when shielded wire is used.)
4190
RPM
4278
PIR
Polling loop rating:
128mA maximum.
POLLING LOOP
21 22 23 24 25
+
-
4192SD
SMOKE
TO RIGHT LOOP
Figure 7-1: Polling Loop Connections to the VISTA-128B