Section 20 – Zone Type Definitions
20-3
Type 22: Disarm*
This is a special-purpose zone type used with 5800
Series wireless transmitters, which will result in
disarming the system when the zone is activated.
Type 23: No Alarm Response
This zone type can be used on a zone when an
output relay action is desired, but with no
accompanying alarm (e.g., for lobby door access).
Type 27: Access Point
This zone type indicates that an input device
(hardwired zone, wireless zone, keypad, access
control relay, etc.) is controlling an access point
entry (e.g., a door). The access point entry relay
can be assigned to an access control relay
(controlled by the VISTA-128B), ECP relay (4204),
or to the access control system independent of the
VISTA-128B.
Type 28: Main Logic Board (MLB) Supervision
This zone type assigns a zone to supervise the
MLB. If communication between the MLB and the
Vista Gateway Module (VGM) fails, this zone will
be displayed on the keypad as “CHECK + the zone
number. Also, if this zone fails, all access control
system (ACS) input zones will also display a
“CHECK.”
Note that these zone types are for use by 5800
Series devices only!
NOTE FOR PANIC KEYS: Keypad panic zones
share the same zone response type for all 8
partitions, but panics may be individually
enabled for each partition.
IMPORTANT! FAULT ANNUNCIATION
Polling loop and RF troubles (zones 988, 990 &
997) will report as trouble conditions only, and as
such, should be assigned zone type 05 if
annunciation is desired. See Polling Loop
Supervision in the 2-Wire Polling Loop Expansion
and RF System Operation and Supervision in the
Wireless Expansion sections for more information.