30-1
SECTION 30
Testing The System
•••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
Battery Test
Dialer Test
Burglary Walk Test
Armed Burglary System Test
Trouble Conditions
Turning the System Over to the User
To The Installer
•••••••••••••••••••••••••••••••••••••••••••••••••
Battery Test
When AC power is present, the VISTA-128B will run a brief battery test every 60 seconds to
determine if there is a battery connected, and will run an extended battery test every 4 hours
to check on the battery’s condition. If the VISTA-128B finds that the battery voltage is low
(less than approximately 11.5V) during one of these tests, it initiates a keypad “SYSTEM
LOBAT” display and a rapid console beeping sound. It also sends a Low Battery report to the
central station (if the dialer feature is used). The console can be cleared by entering any
security code + OFF, and a Restore report will be sent to the central station after a
subsequent test indicates that the problem (disconnected or low battery) has been corrected.
If used, the PS24 will also run a brief battery test every 60 seconds to check that a battery is
connected, and will run an extended battery test every 17 hours to check the actual battery
condition. If the PS24 finds the battery voltage low (less than approximately 23V), it will
open circuit its LOW BATTERY output. Be sure to wire this output to one of the VISTA-
128B's EOLR-supervised zones (zones 3-8; program for 24-hour trouble response (zone type
19) so that the VISTA-128B will initiate the required local annunciation and dialer reports.
Dialer Test
The VISTA-128B may be programmed to automatically transmit test reports to a central
station at intervals ranging from once per hour to once per 999 hours (field *27). UL requires
that a test report be transmitted at least once every 24 hours. The VISTA-128B can be
programmed to send the first report at any time of the day, or on any day of the week after
power-up (field *83).
Burglary Walk-Test (Code + TEST [5])
This test causes the system to sound keypad beeps in response to faults on burglary and non-
fire related 24-hour zones for the purpose of allowing proper zone operation to be checked
without triggering alarms. Note that the system will not trigger alarms for burglary and
non-fire related 24-hour zones, but will trigger fire alarms while this test is active. This test
can only be activated by the installer, a master user or manager user by entering the
corresponding security code and pressing TEST while the burglary portion of the system is
disarmed. UL requires that this test be conducted on a weekly basis.