4. Wiring Run Permitted to No. 4208 Zone Expander (or other
VECTOR RPMS):
Wire Gauge
Max. Wire Run
22 (0.64 mm O.D.) 650 ft (200 m)
20 (0.81 mm O.D,) 950 ft (290 m)
18 (1.0 mm O.D.) 1500 ft (460 m)
16 (1 3 mm O.D.) 2400 ft (730 m)
CABINET MOUNTING THE 4130XT
In buildings using concrete, cinder block or brick wall construction, the
4130XT Security Control can be installed in a wall-mounted metal
cabinet. This cabinet, which measures 8“ (20. 3 cm) W x 8“ (20.3 cm) H
x 2“ (5 cm) D, is available under part No, 4134-8. The 4130XT Control is
mounted in a cut-out in the door of the cabinet, with the function keys,
LEDs and display accessible. The back-up battery is installed within the
cabinet Also available for use within the cabinet are connector blocks
with which the 4130XT’S flying leads can be tied to the interface wiring
(from protection zones, etc.). See Diagram B.
Mounting the 4130XT in the Cabinet
Note that there is a mounting flange on each side of the opening m the
cabinet door.The Control is secured to these flanges with the two self-
tappmg screws supphed. Positton the Control (wtlh back cover removed)
in the opening and secure as follows, referring to Diagram A.
On the left-hand side, insert the No. 6 x 1” self-tapping screw through the
front of the Control into the left flange as shown, and secure. Do not fully
t!ghten yet.
To secure the right-hand .wde, mserf the No, 4 x %“ self-tapping screw
into the other flange from the rear. and screw into the slot in the plastic
4208 ZONE EXPANDER
1.
Physical: Width
3-7/8” (9.8 cm)
Height:
7“(178 cm)
Depth:
1-3/8” (3.5 m)
2. Electrical:
Voltage Input
8-11 Volts
(w/l KHz
Modulation)
Current Drain: 16 mA
at the rear of the Control, as shown, Making sure the Control is straight,
tighten this screw fully,
Fully tighten the screw on the other side, then insert the VISTA XT name-
plate into the recess to cover the screw, as shown in Diagram A.
Mounting Cabinet on Wall:
Four holes have been prowded m the back of the cabinet for mounting
purposes -2 keyhole slots at the top and 2 holes at the bottom. Knock-
outs are prowded at the sides [% “(2.2cm) diameter], plus one at the rear
[1 -%” (4.5 cm) diameter].
1. If the interface wiring is being brought through the wall, make the
required opening In the wall for the wmrig.
2. Remove the desired knockout m the cabinet to allow entry of the inter-
face wiring.
3. Place the cabinet on the wall m the desired position and mark the loca-
tions of the mounting holes.
Note The cabinet may be mounted with only 2 screws at the keyhole
slots, if desired.
4. Drill mounting holes in the wall and insert anchors. Mounl the cabinet
securely to the wall with four (or 2) screws.