FUNCTION
ADDRESS
MULTIPLE ALARMS
●23
DISABLE TAMPER
*24
DETECTION IN
EXPANSION ZONES
10-17
DISABLE DURESS
●25
REPORTING IN
ADEMCO HIGH
SPEED FORMAT
INTERNAL ALARM “26
SOUND SELECTION
TEST REPORT
*27
INTERVAL
❑
COMMENTS: Enables the system to permit mutiple audible alarms from a protection zone during one armed inter-
val (as opposed to only one alarm).
Enter O (only one alarm) or 1 (multiple alarms, but not more frequently than allowed by alarm time-out) Selection
has no impact on the number of communciation messages transmitted.
❑
COMMENTS: Only applicable if No, 4190WH RPMs are used to provide expansion zones. Enter 1 to disable
tamper detection (disables tamper detection in 4190WH or tamper detection is not applicable because other
devices are used to provide expansion zones), Enter O to enable tamper detection (opening of the 4190WH case).
❑
COMMENTS: Only applicable if Ademco High Speed Format is selected. Enter 1 to disable duress reporting or O
to enable duress reporting.
•1
COMMENTS: Enter 1 to select a ‘(sweeping” sound (applicable only to non-UL usage) from the control’s internal
alarm sounder, enter O for a louder, steady sound (required for UL Listed usage).
NOTE: Since remote Consoles can only produce a “steady” sound, program the control for steady tone (0) if they
are used in the system.
❑
COMMENTS: Determines time period between test reports.
Enter O (no report), or
1 (12 hours), 2 (24 hours)or3(168 hours).
Must be used in conjunction with Data Fields *83 and *68 (location 5), Select a non-zero entrv if automatic low bat.
tery testing under load is desired.