VISTA-402-PartitionSecurity SystemInstallation and Setup Guide®N7001V4 7/98Previous Menu
SECTION 18 Data Field Descriptions...18-1SECTION 19 #93 Menu Mode Programming...
*43 DIAL TONE DETECTION[1]Determines whether the control will wait for a true dial tone before dialing, or if it willwait for a predetermined delay
*50 SESCOA/RADIONICS SELECT[0]Enter 0 if Radionics format is to be used with hexadecimal 0-9, B-F reporting. Enter 1 ifSescoa format is to be used w
*83 FIRST TEST REPORT TIME(00 12 00)|||Enter the day (00-07) and time (00-23 hours/00-59 min.) that the first Test report shallbe transmitted.Enter 0
*89 RESTORE REPORT TIMING[0]Enter 0 for instant Restore report as zone restores.Enter 1 for reporting after bell timeout if zone restored. Enter 2 f
1*32 RF RECEIVER TYPE[0]Enter 0 if no receiver is being used.Enter 1 if using 4281 series receivers.Enter 2 if using 5881 series receivers.1*33 TOUC
1*46 AUXILIARY OUTPUT MODE[0]Enter 0 if ground start output is required.Enter 1 if the auxiliary output will be used to produce an open/close trigger
1*60 ZONE 5 AUDIO ALARM VERIFICATION[0]Enter 1 if 2-Way Audio (AAV) is being used.Enter 0 if AAV is not being used. Must be 0 for UL installations.1
Enter the start and end weekends for daylight savings time as follows: 1=first;2=second; 3=third; 4=fourth; 5=last; 6=next to last; 7=third from last.
VISTA-40 Installation Instructions18-14
SECTION 19#93 Menu Mode Programming•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ #93 Main Menu Options♦ Zone Programming♦ Sequenti
Armed Burglary System Test ...25
SEQUENTIAL LEARN?0=No 1=YesFor programming the following:• Input device type for zone (whether RF, polling loop, etc.)• Enrolling serial number
The following is a list of commands used while in the Menu Mode.#93 Menu Mode Key Commands#93 Enters Menu mode[✱] Serves as ENTER key. Press to have k
00 PROG AS BR: 3 A123-4567 3In this example, the serial number is A123-4567. Onceenrolled, the upper left-hand button of the program tool ca
10 PARTITION 2Enter the partition number (1–2) you are assigning this zoneto.Press [*] to continue.10 REPORT CODE1st 03 2nd 12 3CEnter the repor
3412(ALWAYS USE)LOOP5801ENROLL AS "UR" OR "RF"LOOP15802/5802CPENROLL AS "BR"LOOP15802MNENROLL AS "UR" OR "
10 INPUT S/N Axxx-xxxxThis prompt is displayed if 1 (YES) is entered in response tothe "LEARN S/N?" prompt. The serial number may be en
Sequential Mode ProgrammingUsually, serial numbers are enrolled during Zone Programming. If not, use #93 Menu Modeto enroll serial numbers (for examp
TECHNOLOGY TYPEWIRELESS 0Default ↑ Enter the type of device(s) to be enrolled as follows:0 = Wireless (Default)1 = Polling Loop2 = BothPress [∗] to c
10 INPUT S/N A 022-4064↑ Serial #The system will enroll the first serial number heard, displaythe serial numbers, and cause the keypad to beep
Alpha Descriptors ProgrammingGeneral Information• You can program a user-friendly English language description/location for all protectionzones, rela
List of Figures••••••••••••••••••••••••••••••••••••••••••••••••••Figure 3-1: Mounting the PC Board ...
3. Enter the descriptor for that zone.Use one of two methods as follows:(Assume, for example, that the desired description for Zone 1 is BACK DOOR)a)
Custom WordsUp to 20 installer-defined words can be added to the built-in vocabulary. Each of the 20"words" can actually consist of several
Partition Descriptors1. Select "Part DESCRIPT." Mode. The system will ask for the partition number desired.Enter the number as a single-key
ALPHA VOCABULARYFor Entering Alpha Descriptors. To select a word, press [#] followed by the word's 3-digit number.Bulleted words in bold face typ
Device ProgrammingThis menu is used to program keypads, receivers and relay modules.From Data Field Programming mode, press #93 to display "ZONE
SOUND OPTIONIf device type 1 (Alpha Keypad) or 2 (Fixed Keypad) is selected,this prompt will appear. Keypads can be individuallyprogrammed to suppres
START (STT)The "START" programming determines when and under what conditions the devicewill be activated. The following START options are a
If a "SYSTEM OPERATION" is chosen, that operation will cause the device tode-activate. The different choices for "ZONE TYPE" and
02 START: ZN TYPEA Zone Type/System Operation can be used instead of or inaddition to an Event/Zone List combination to start the relayaction. If a Z
RESTRICTION1=YES 0=NOThe system may have some devices, which are not intended tobe under end user control, such as relays activating fire doorsor mac
How To Use This ManualThis manual is written to accommodate both the new and the experienced installer ofADEMCO products. A general description of the
Zone List ProgrammingAfter all relays have been programmed, upon entering 00 at the "ENTER RELAY NO."prompt, you will be asked to enter a Zo
To enter relay voice descriptors, do the following:1. From data field programming mode, press #93 to display the "ZONE PROG?" prompt.2. Pr
Relay Voice Descriptors and Custom Word Substitutes VocabularyWord IndexAir ...116Alarm...255And...
Custom Word Substitutes for VIP Module AnnunciationA substitute word can be programmed for each of the 20 custom words used in your alphazone descript
VISTA-40 Installation Instructions19-26
SECTION 20System Communications••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦General Information♦ Telephone Line Connections♦A Suc
1. To prevent the risk of shock, disconnect phone lines at telco jack before servicing the panel.2. If the communicator is connected to a telephone li
The following describes each format in greater detail.3+1 and 4+1 StandardFormatsComprised of a 3- (or 4-) digit subscriber number and a singledigit r
Restore SSS(S) R SSS(S) R SSSS RZAlarm RRR(R) ZAC Restore SSS(S) RASSS(S) RASSSSRA AcRARARA(RA)AcLoBat Res. SSS(S) RLSSS(S) RL SSSS RLLBRLRLRL(RL)LB
The status channel might have one of the following conditions:1 = DURESS (For Duress Plus Channels 9-15 Only)2 = OPENING3 = BYPASS (For Channels 1-8 O
Conventions Used in This ManualBefore you begin using this manual, it is important that you understand the meaning of thefollowing symbols (icons).ULT
TABLE OF CONTACT ID EVENT CODESCode Definition110 Fire Alarm121 Duress122 Silent Panic123 Audible Panic131 Perimeter Burglary132 Interior Burglary134
Loading Communication DefaultsTo help expedite the installation, the system provides 4 different communication defaults(Low Speed, Ademco Express, Ade
*50 SESCOA/RADIONICS SELECT [0] Radionics*51 DUAL REPORTING [0] no*52 STANDARD/EXPANDED REPORT FOR PRIMARY[0] [0] [0] [0] [0] [0]standardAlarm Rstr B
*45 PRIMARY FORMAT [3] Ademco Express*46 LOW SPEED FORMAT (Primary) [0]*47 SECONDARY FORMAT [3] Ademco Express*48 LOW SPEED FORMAT (Sec.) [0]*49 CHECK
*45 PRIMARY FORMAT [2] Ademco High Speed*46 LOW SPEED FORMAT (Primary) [0]*47 SECONDARY FORMAT [2] Ademco High Speed*48 LOW SPEED FORMAT (Sec.) [0]*49
*45 PRIMARY FORMAT [1] Ademco Contact ID*46 LOW SPEED FORMAT (Primary) [0]*47 SECONDARY FORMAT [1] Ademco Contact ID*48 LOW SPEED FORMAT (Sec.) [0]*49
VISTA-40 Installation Instructions20-12
SECTION 21Downloading(Remote Downloading is not a UL Listed feature)••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Informa
3. COMPASS DOWNLOADING software, may be purchased from ADEMCO. This softwareis available on 3-1/2" diskettes, or CD ROM and includes a complete
On-Line Control FunctionsThe following functions can be performed while on-line with a control panel:• Arm the system in the AWAY Mode; disarm the sy
SECTION 1.General Description•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General♦ Features••••••••••••••••••••••••••••••••••••••
Connecting a 4100SM Module for Direct Wire DownloadingThe VISTA-40 can be downloaded without using a modem or telephone line by usingADEMCO’s V-Link®
SECTION 22Setting The Real-Time Clock••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Setting the Time and Date
VISTA-40 Installation Instructions22-2
SECTION 23User Access Codes•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ User Codes & Levels of Authority
Auth Title0 Installer1Master2 Manager3 Operator level A4 Operator level B5 Operator level C6DuressLevel 0: Installer (User 1)• Programmed in field *00
Level Title Functions Permitted3 Operator A Arm, Disarm, Bypass4 Operator B Arm, Disarm5 Operator C Arm, Disarm only if armed with same code• Operato
Open/Close Reporting Note: When adding a user, the system will only prompt forOpen/Close reporting capability if the installer is adding the user. Wh
To ADD a Master, Manager, or Operator CodeDuring user code entry, normal key depressions at other keypads in a partition will be ignored.However, pani
Global Arm ?0 = NO , 1 = YESPress 0 (NO) or 1 (YES), depending on whether or not this userwill be allowed to arm more than one partition via Global Ar
To Delete a Master, Manager, or Operator CodeEnter your code†+ [8] + new user # (02-69) + your code again.†Or Master or Manager code, but must be a co
Addressable Devices• Supports up to sixteen addressable devices (any combination of remote keypads, RFreceivers and relay output modules.Keypads• Sup
VISTA-40 Installation Instructions23-8
SECTION 24Keypad Functions••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Arming Functions♦ Global Arming♦ Acc
Arming FunctionsThe following is a brief list of system commands. For detailed information concerning systemfunctions, refer to the User's Manual
Global ArmingIf enabled for the user, the alpha keypad will display the following:ARM ALL ?0 = NO , 1 = YESIf NO, the keypad prompts for arming e
Viewing Capabilities Of A UserThe alpha keypad will display the partitions that a user is authorized for, the user number,and the authority level for
For the panic functions to be of practical value, the system must be connected to a central station.Manual Relay Activation Mode (#70 Mode)The system
VISTA-40 Installation Instructions24-6
SECTION 25Testing The System••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Battery Test♦ Dialer Test♦ Burglary Walk Test♦ Armed Bu
Open and close each protected door and window in turn. Each action should produce 3 beepsfrom the keypad. Walk in front of any motion detectors. Li
Other System Messages• "COMM. FAILURE" (alpha) or "FC" (fixed-word) at the keypad indicates that a failureoccurred in the telepho
Programming Features• Programming can be performed at the office prior to installation, or on the job sitedirectly from the keypad.• Can be download
Contacting Technical SupportPLEASE, before you call Technical Support, be sure you:• READ THE INSTRUCTIONS!• Check all wiring connections.• Determi
APPENDIX ARegulatory Agency Statements••••••••••••••••••••••••••••••••••••••••••••••••••UL Installation RequirementsThe following requirements apply t
FEDERAL COMMUNICATIONS COMMISSION (FCC) STATEMENTThis equipment has been tested to FCC requirements and has been found acceptable for use. The FCC re
CANADIAN DEPARTMENT OF COMMUNICATIONS(DOC) STATEMENTNOTICEThe Canadian Department of Communications label identifies certified equipment. This certifi
VISTA-40 Installation InstructionsA-4
APPENDIX BDIP Switch Tables••••••••••••••••••••••••••••••••••••••••••••••••••B-1
DIP SWITCH TABLES FOR ADDRESSABLE POLLING LOOP DEVICES4208 ZONE EXPANDERDIPSHOWN SET FORID 10 (A)SIDE VIEW(UP)12345UPDNUPDNPOS.1: LOOPS 1 & 2RESP
DIP SWITCH TABLES FOR POLLING LOOP DEVICES4275 PIRMIRRORDIPSHOWN SET FORID 10 (A)SIDE VIEW(UP)123456 7UPDNPOS 6: UP (A), DN (B) = INST. MODEDN (A), U
DIP SWITCH TABLES FOR 5700 RF SYSTEM WIRELESS DEVICESHOUSE ID (1 SHOWN)HOUSE ID (1 SHOWN)HOUSE ID (1 SHOWN)123456UPDN12345UPDN123456 78UPDN123456 7891
APPENDIX CSpecifications•••••••••••••••••••••••••••••••••••••••••••••••••VISTA-40 ControlPhysical:12-1/2"W X 14-1/2"H X 3"DElectrical:V
Zone Reports• All 64 zones can report to a central station using any standard reporting format.Callback• Callback defeat option for downloading.Real
6128 Remote KeypadPhysical: 5-3/4" W x 4-3/4" H x 1" D (146mm x 121mm x 26mm)Electrical: Voltage Input: 12VDC; Current Drain: 30mAInter
APPENDIX DIndex•••••••••••••••••••••••••••••••••••••••••••••••••##70 Relay Mode... 24-5#93 Menu
Arming Maximum ... 24-2Arming Stay...
ENTRY DELAY #2 ... 18-1Entry Errors ...
Operator Level Codes ... 23-2Output Control...
TOUCHTONE OR ROTARY DIAL... 18-4Transmitter Battery Life... 7-5, 7-8Transmitter ID
VISTA-40 Installation InstructionsD-6
WARNING!THE LIMITATIONS OF THIS ALARM SYSTEMWhile this System is an advanced wireless security system, it does not offer guaranteed protection against
ADEMCO LIMITED WARRANTYAlarm Device Manufacturing Company, a Division of Pittway Corporation, and itsdivisions, subsidiaries and affiliates ("Sel
++-N.C.N.C.N.O.2k EOLR(note 1)2k EOLR(note 1)+-+-+-BELLSIRENNO CONNECTIONTRANSFORMER16.5VAC, 40VAADEMCO No.1361(IN CANADAUSE No. 1361CN)or 4300 TRANS-
SECTION 2Introduction To The Partitioned System••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Theory of Partitioning♦ Global Parti
165 Eileen Way, Syosset, New York 11791Copyright © 1998 PITTWAY CORPORATION¬19$lN7001V4 7/98
K3500 7/98ADDENDUM TO: VISTA-40, VISTA-50P, VISTA-50PULINSTALLATION INSTRUCTIONSThis Installation Instruction
Global Partitioning Features and ResourcesIn any system, certain physical system components and features are shared by all partitionsor assigned to a
SECTION 3Installing The Control•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Mounting the Cabinet♦ Mounting the PC Board♦ Installi
DETAIL BSIDE VIEW OF SHORTMOUNTING CLIPSDETAIL A SIDE VIEW OFBOARD INSERTEDINTO SLOTSFigure 3-1: Mounting the PC BoardInstalling the Lock1. Remove t
Incoming phone line and handset wiring is connected to the main terminal block as follows(see Figure 3-3):TB1-26: Local Handset (TIP)TB1-27: Local Han
VISTA-40 Installation Instructions3-4
SECTION 4Installing The Keypads•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Wiring the Keypads♦ Powering Add
Keypads may be wired to a single wire run or individual keypads may be connected toseparate wire runs. The maximum wire run length from the panel to
Mounting the KeypadsThe keypads can be either surface mounted directly to a drywall, or to a single or doublegang electrical box, or flush mounted (us
Preliminary Checkout ProcedureIf you want to check that the system is working before connecting field wiring from zones anddevices, do the following:1
SECTION 5Basic Hardwired Zones 01-09•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Common Characteristics of Hardwired Zones 1-9♦ W
ADDENDUM: Bell Supervision (continued)2Diagram 1: Wiring Non-Polarized Burglary Indicating DevicesPANEL BELLPANEL BELL+-BELLBELL}HORNNON- POLARIZED BU
++-N.C.N.C.N.O.2k EOLR 2k EOLR+-++-N.C.N.C.2k EOLR 2k EOLR++-N.C.++-N.C.N.C.2k EOLRSMOKEZone resistance (Excluding EOLR):ZONE 1,8: 100 OHMS MAXIMUMALL
2k EOLRZONE 1SMOKE(+)(-)2-WIRE SMOKEDETECTOR 1011(+)(-)Figure 5-2: 2-Wire Smoke Detector Connected to Zone 1.Compatible 2-Wire Smoke DetectorsYou may
4-WIRESMOKEDETECTOREOLRELAYNO CONNECTION{TOPANELZONE(ZONE 2-8){TOPANELAUXILIARYPOWER(TERMINALS 6, 7)CNCNORESETRELAY 1, 2, 3 OR 44204 RELAY MODULENOTES
2122GLASSBREAKDETECTORZONE 8(+)(-)LATCHING TYPE GLASSBREAK DETECTOR LOOP2000 OHMSEOLRFigure 5-4. Wiring Latching Glassbreak Detectors to Zone 8After
Restore any faulted zone(s) as necessary (also make sure that you have connected a2000 ohm EOL resistor across the terminals of unused zones). When t
SECTION 62-Wire Polling Loop Expansion(Zones 10 through 64)•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Polling Loop Overview♦ Co
Wiring/Addressing RPM DevicesAll devices on the polling loop must be wired in parallel to the [+] and [-] polling loopterminals of the control panel (
2. Wire each device to the polling loop, making sure to use correct polarity when makingconnections (refer to the device's instructions). If yo
Compatible Polling Loop Devices (cont’d)4278 Quad PIR• Quad element PIR with built-in RPM(connects directly to the polling loop).• DIP switch-progr
Compatible Polling Loop Devices (cont’d)4959SN Aluminum OverheadDoor Contact• 24-inch armored cable• Serial Number ID programmed by controlpanel.750
ADDENDUM: Battery Backup (continued)3Note: The cabinet supplied with the VISTA-40 and VISTA-50P panels can house up to 12V, 14AHbatteries (two 12V, 7
4. If the following is displayed, press the [✴ ] key to display the faulted zone(s):DISARMED Press ✴to show faults5. Restore any faulted zone(s) as
SECTION 7Wireless Zone Expansion••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Common Characteristics of Wireless Zones♦ Wireless
In Canada, 5800 systems must use 5882 Series receivers: 5882L/5882H. Information in thismanual relative to the 5881 Receivers applies as well to the
RF System Installation Advisories1. Place the receiver in a high, centrally located area for best reception. Do not place it on ornear metal objects.
Installing the 5800TM ModuleInstallation of this module is necessary only if you are using one or more Bi-directionaldevices (5827BD, 5804BD).The 5800
Transmitter Supervision• Each transmitter (except 5701 and 5727) is supervised by a check-in signal that is sent tothe receiver at 70-90 minute inter
Wireless Zone Assignments for 5700 Series TransmittersEach RF zone can be assigned any zone response type, such as entry/exit, interior, perimeter,etc
Compatible 5700 Series TransmittersModel Product Zone Num. Description5742 Audio Discriminator 1-63• For use in unoccupied areas todetect the sound o
Transmitter SupervisionExcept for some transmitters that may be carried off premises (5802, 5802CP, 5803, 5804,5808BD, 5827, and 5827BD), each transmi
Compatible 5800 Series TransmittersModel Product Input Type Description5801 Wireless PanicTransmitterUR or RF• Has four pushbuttons, each witha uniqu
K3500 7/98 ®165 Eileen Way, Syosset, NY 11971Copyright 1998 PITTWAY Corporation
Compatible 5800 Series Transmitters (cont’d)Model Product Input Type Description5817 Multi-Point UniversalTransmitterRF• Has three unique input (loop
Checkout Procedure for Wireless ZonesTransmitter ID Sniffer ModeUse the Transmitter Sniffer Mode to test that transmitters have all been properlyprogr
VISTA-40 Installation Instructions7-12
SECTION 8J7 Voltage Triggers••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Ground Start Trigger Setup♦ Remote
1 2 3 4 5 6 7 8 9GRAYYELLOWWHITEREDGREENBROWNBLUEBLACKGROUNDOUT 1GROUNDOUT 2GROUNDOUT 3GROUNDOUT 4J7 CONNECTOROUT 1: GROUND START OR OPEN/CLOSEOUT 2
1 2 3 4 5 6 7 8 9GRAYYELLOWWHITEREDGREENBROWNBLUEBLACKGROUNDOUT 1GROUNDOUT 2GROUNDOUT 3GROUNDOUT 4J7 CONNECTORIF USED.1. OUT 1 IS NO LONGERUSABLE FO
Wiring for the Remote Keypad SounderConnect the piezo sounder to the panel’s positive auxiliary power output and to Output 1 onthe J7 connector as sho
NOTE:The tamper switch need not beused for UL Household Fire orBurglary installations. The tamper switch must be connected to an EOLRsupervised zone p
With Alarms Present:A momentary short across Zone 7 will silence alarm bell and keypad sounds, and will disarmthe system if it was armed. The keyswit
GND (GRAY)BURG/AUDIBLE PANIC (BROWN)REQUIREDSILENT PANIC/DURESS (BLACK) OPTIONALFIRE (RED) OPTIONAL7720 RADIOFAULTFAULTZONE 1ZONE 2ZONE 3ZONE 4GNDSEE
1 2 3 4 5 6 7 8 97720 ULF RADIOSEE 7720 ULF INSTRUCTIONS FORMORE DETAILED INSTALLATIONINFORMATIONFAULT4142TRCABLE4142T
SECTION 9Relay Outputs andPowerline Carrier Devices••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Relay Basics♦ Wiring the 4204 Re
3. When mounted remotely, homerun each module to the control. The table below showsthe maximum wire run lengths from the control to each 4204.Wire G
Wiring the 4300 TransformerPowerline Carrier devices (such as X-10, ACT, Leviton) are either plugged into standard ACoutlets or wired into the AC elec
VISTA-40 Installation Instructions9-4
SECTION 104285/4286 VIP Module••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Mounting the VIP Module♦ Wiring
Mounting the VIP ModuleThe VIP Module may be mounted in the control cabinet if space is available, or on the side ofthe cabinet or adjacent to it. Pry
YELLOWNO CONNECTIONREDBLACKGREENTO CONTROL PANEL KEYPAD CONNECTIONSKEYEDHEADER1 2345 6 7NOCONNECTION4286 VIP MODULEANSWERING MACHINEPREMISESANSWERINGM
VISTA-40 Installation Instructions10-4
SECTION 11Audio Alarm Verification (AAV) Unit••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ AAV Module Operat
Recommendations for Proper ProtectionThe Following Recommendations For The Location Of Fire And Burglary Detection Devices Help ProvideProper Coverage
messages triggered during ongoing conversation will be held until either the AAV Modulesignals that it is inactive, or the 15-minute timeout occurs.On
CONTROL/DIALER HEADERNOTE:REFER TO AAV MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND MICROPHONE.•••••EAGLE1250671617272628 2930}ZONE 5(–)(
Programming Audio Alarm Verification Module Options1. With at least one 2-line alpha keypad (6139) wired and set to a proper address,temporarily appl
SECTION 12External Sounders••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Alarm Output Supervision♦ Wiring th
Alarm Output SupervisionWhen supervision is enabled, the panel monitors the alarm output wiring for open and shortcircuit faults while the output is i
Wiring the Alarm OutputUL985 Household Fire or Combination Household Fire/Burglary InstallationsFor installations, which must provide UL Listed protec
ULThis control complies with National Fire Protection Association (NFPA) requirements for temporalpulse sounding of fire notification appliances.Non-U
SECTION 13Final Power-Up Procedure••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Connecting the AC Transformer♦ Earth Ground Conne
Earth Ground ConnectionsIn order for the lightning transient protective devices in this product to be effective, thedesignated earth ground terminal m
Polling Loop Current Draw WorksheetRPM Device Current # Units Total Current998MX PIR 1mA4191SN Contact 1mA4194 Contact 1 mA4192SD Photo Smoke 0.4 mA41
Table of Contents••••••••••••••••••••••••••••••••••••••••••••••••••SECTION 1 General Description 1-1General...
Alarm Output Current Draw WorksheetDevice Current # Units Total CurrentTotal Alarm Output∗∗For UL fire or fire/burglary installations 750mA maximum in
SECTION 14Event Log Options••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Programming Event Log Options♦ Even
Event Logging ProceduresIn order for proper time and date stamping to occur, the system's real-time clock must be set.Refer to the Setting the Re
To display the events in a particular category, press [8] at the desired category screen.When Display Mode, the most recent event is displayed. Press
VISTA-40 Installation Instructions14-4
SECTION 15The Mechanics of Programming•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Using Data Field Program Mode♦ System and Comm
The factory-loaded defaults (*97) enable keypad addresses 00-03 only. A keypad set to one ofthese addresses must be used to program the system.Enterin
SUMMARY OF DATA FIELD PROGRAMMING COMMANDS*91Select partition for programming partition-specific fields*92Will display the software revision level of
PROGRAMMING PARTITION-SPECIFIC FIELDSPress *91 to select a partition.↓Enter the partition to be programmed.↓Enter a partition-specific field # and mak
SECTION 16Zone Type Definitions••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Zone Number Designations♦ Zone Type Definitions•••••
SECTION 8 J7 Voltage Triggers ...8-1General Information...
Type 02: Entry/Exit #2 BurglaryThis zone type provides a secondary entry delaywhenever the zone is faulted if the panel is armedin the AWAY and STAY M
Type 22: Disarm*This is a special-purpose zone type used with 5800Series wireless transmitters, which will result indisarming the system when the zone
VISTA-40 Installation Instructions16-4
SECTION 17Zone Index/Zone Type Defaults••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Zone Index♦ Zone Type Defaults••••••••••••••
Zone Type DefaultsFollowing are the zone type defaults for zones on the VISTA-40:Zone # Zone Type01 0902 0303 0304 0305 0306 0307 0308 0309 0310–64 00
SECTION 18Data Field Descriptions••••••••••••••••••••••••••••••••••••••••••••••••••The following is a description of all data fields provided by this
*14 ZONE 9 RESPONSE TIME[0]Enter 1 to set fast response mode (10 msec) for appropriate devices wired to zone 9.Enter 0 for normal response (350 msec)
*23 MULTIPLE ALARMS (partition-specific)[0]Determines whether or not more than one alarm can be sounded in a given zone duringan armed period. Note
*29 QUICK ARM (partition-specific)[1]Enter 1 to enable arming of the burglary system in AWAY, STAY, INSTANT orMAXIMUM modes by using the # key inst
*36 DOWNLOAD ID NUMBER||||||||Enter eight digits, 00-09; A-F (10-15). Only applicable if downloading will be utilized.Make entries as 2-digit numbers
Comentarios a estos manuales