BASIC 8 HARD-WIRED ZONES (Zones 1-8)
GENERAL
All zones have a 350 milh-second resWnse and can be assigned any zone t~.
INFORMATION All zones provide class B (style B) supervision using a 2K EOL resistor (m
610-7, supphed). The panel also supewises the zone wiring for eatih gro~
fauns.
When programmed for fire warning usage, all zones can monitor 4-wire smke
detectors (zone ty~s 9, 16), N.O. fire alarm initiating devices (zone types 9, 17)
or N.O. sprinkler system superviwry devices (zone type 18). When programmed
for burglary usage, all zones can mcnitor N.O. or N.C. alarm initiating devices. Use
any UL fisted N.O. or N.C. device not requiring power from the panel. Use only
those 4-wire smoke detectom Mstedbelow.
Note that power for 4-wire smoke detectors is supptied by the pane~s auxitiary
power #1 output and thb power mst be switched using the ~n~n auxi[ary relay
to allow the detectors to be reset via the second entry of an OFF sequenm ~.e.:
semrity code + OFF key) at a mnsole folbwing an slam. Also mte that a System
Sensor A77-71 6-01 EOL relay module must be used to supewise the power
mnne~lons to 4-wire smoke detectors. See the AUXILIARY RELAY section for
programming and wiring information. Zones which are programmed for fire with
alarm verification respnse (zone type 16) should only be used to monitor smoke
detectors.
Connect N.C. devices In series with the zone wires and connect N.O. devices
across (In parallel with) the zone wires. Obsewe polarity when wiring smoke
detectors. Connect the 2K EOL resistor across the
zone wires at the last device.
The maximum zone resistance is 100 ohms for zones 1, 2 and 6 and 300 ohms
for all other zones (excluding the 2K EOL resistor).
Compstlble 4-Wire Smoke Detectors
You may use as many 4-tire smoke detectom as can be powered from the paners
auxitiary power 1 output without exceeding this outpu~s rating (see the
POWERING THE SYSTEM section for auxiiary PO
wer ratings)
Photoelectric, direct wire
I System Sensor 2412
w
Photoelectric w/heat sensor, dhect wire
! System Sensor
2412TH
Ionization, direct
wire
I System Sensor 1412
ZONES 1 & Z 2-~RE
These zones have the added cspabihty of suppoting 2-wire smke detectors.
SMO=
DETECTORS
Each zone provides enough sta~by current (2 MA) to pwer up to sixteen of the
smoke detectors fisted bebw. Each zone provides only enough alarm current (20
mA) to power one smoke detedor in the alarmed state. When assigned zone
type 9 or 16, the second entry of an OFF sequewe at a console will interrupt
power to these zones to albw detectors to be reset folbwing an alanw.
Compstlble 2-Wire Smoke Detectors
You may use up to sixteen 2-wire smke detectors on zone 1 and on zone 2 as
found in the table below.
DETECTOR TYPE
DEVICE MODEL #
Photoelectric w/heat sensor, direct wire
System Sensor 2300T
Photoelectric, dir~ wire
System Sensor 2400
Photoelectric w/heat sensor, direct wire
System Sensor 2400TH
Photoelectric w/B401 B base
System Sensor 2451
Photoelestnc w/heat sensor and B401B base
System Sensor 2451TH
Ionization, direct wire
System Sensor 1400
Ionization w/B401 B base
System Sensor 1451
Photoelectric duct detect. w/DH400 base
System Sensor 2451
Ionization duct detector w/DH400 base
System Sensor 1451DH
NOTE These smoke detedors are Listed for use wth the 5140XM and are the only 2-wire
smoke detedors that may be
ussd.
w
-8-