BATTERY
As a function of the 5140XM control, battery voltage is montored once every 60
SUPERVISION
seconds. Under normal Wndifions the battery votiage should be approximately
13.65VDC. If battery voltage drops below approx. 11.5 volts, a low battery
message is sent to the central station and annunciated on the local mn$eis.
Battery lead supervision can be tested from the panel. The recomme}.>
procedure is to disconnect the battery harness from the 5140XM at the tab
facations found on the left side of the 5140XM. Within 60 seconds a low battery
signal will be sensed and the control bagina communicating the information to the
central station.
BACK-UP POWER
The panel provides a circuit for float charging a 12 VDC, 12 AH rein/34.4 AH max
CALCULATIONS
lead acid (gel cell) back-up battery. The. float charging voltage is set to approx.
13.7 VDC. UL requires that the battery’s capacity be sized to provide 24 hours of
standby time for fire or for comMnaton fhe/burglary appkcations. This can be
*ne as follows:
1.
2.
3.
Rll out the POLLING LOOP CURRENT DRAW WORKSHEET, shown on nexf
page, to determine the total current drawn from the poifing loop (skip this step
if ~lling faop not used).
Hll out the TOTAL STANDBY/AMRM LOAD WORKSHEET, shown on next
page, to determine the total standby and alarm load drawn from the pane~s
pwer supply.
Hll out the BATTERY CAPACIW CALCULATION WORKSHEET, sbwn on
next Daae. to determine the reauired caDacffv for the backuo batferv. Select
one of fie batteries given in the BA~ERY SELECTION TABLE, sfiown on
the nefl page.
POWER-UP Connect all zone, polling loop, mnsole, auxifiary device and bell circuit wiring.
PROCEDURE Wire and plug-in the 1451 transformer. After a few semnds the console’s green
POWER indicator should tight. If not, check that the 1451 transformer is
supplying proper voffage to the panel (about 17-19.5VAC when the power tine
voitaae is 11O-120VAC).
Mea~ure the voffage across the “+” and “-” battery teminals on the main PCP ‘o
check that there is proper float charging voltage (13.5-13.8VDC). If not,\_,2
auxiliary power terminals may have been loaded in excess of their ratings.
Connect the back-up battery(s) using the batte~ harness supplied as shown
below. The panel performs a brief teat every 60 seconds to determine if there is a
battery connected, and performs an exended test eve~ 24 hours to check the
battery’s condiion, and provides a “SYSTEM LOBA~ indication when it finds
that the batiev vokage is bw (less than approx. 11 .5VDC; see the TESTING THE
SYSTEM section for mre information). Batteries which are low in vokage may
take up to 46 burs to fully recharge.
The consoles will display the installer’s message (default message is
“DISARMED-READY TO ARM”) if all zones are intact and there are no system
problems. If Mt diWlayed, correct zone and system problems as needed.