SYSTEM ZONES (Zones 70- 99)
GENERAL
Aside from the 64 hardwire and polfing loop sensor zones, the 5140XM provides
INFORMATION a number of additional zones which are dedicated to monitoring various aspects
of system behavior. These system zones are listed below. The “system zor “
number appears in the console display window when a fault contition associati
with this zone is detected. The zone types programmed in field 3’10 (for zones
70-75) and field ’05 (for zones 95-99) determine the panel’s response to “system
zone” faults.
Zone #70: Bell Output 1: Monitors bell 1 outpu~s supewision status (if enabled
at installation time). See the BELL CIRCUIT OUTPUTS section for
more information.
Zone #71: Bell Output 2: Monitors bell 2 outpu~s supervision status ct enabled
at installation time). See the BELL CIRCUIT OUTPUTS section for
more information.
Zone #72: Earth Ground: Monitors the panel’s field wiring to determine if an
eatih ground fault exists. Ttis zone’s default type is
set to [19] (24
hour trouble) to provide a trouble response to earth ground faults.
When the panel detects an earth ground fault caused by tampering
with (i.e.: drilling through) the Ademco AB12 grade A burglary bell
box, it overrides the zone 72 fault response and instead ttiggers a
zone 6 alarm (if enabled in field 3’1 7).
Zone #73: J2 Input: Monitors the status of Input 1 on the main PCB J2 header.
Input 1 can be used to monitor the “Xmit Okay” signal from the
7620ULF LORRA. See the TRIGGER OUTPUTS section for more
information.
Zone #74 Dialer Line 1: Monitors the supervision status of the main dialer
output (K enabled at installation time). See the DIALER OUTPUTS
section for more information.
Zone #75: Dialer Line 2: Monitors the supe~ision status of the optional
5140DLM back-up dialer module’s output (if installed/enabled
installation time). See the DIALER OUTPUTS section for rob_,
information.
Zone #76: Auxiliary Relay: Assigned to the built-in auxiliary relay for the
purposes of allowing the operation of this relay to be bypassed.
Wnce the auxilia~ relay is not supervised, this zone does not monitor
anytting and cannot be assigned a zone type.
Zone #77 LORRA Triggers: Assigned to the LORRA triggers on the main PCB
J2 header for the purposes of allowing the operation of these
triggers to be bypassed. Since the LORRA triggers are not
supervised, this zone does not monitor an~hing and cannot be
assigned a zone type.
Zone #95: Keypad Panic: Activated by simultaneous depression of the console
~] and [1] keys. See the KEYPAD FUNCTIONS section for more
information.
Zone #96: Keypad Panic: Activated by simultaneous depression of the console
[#] and [3] keys. See the KEYPAD FUNCTIONS section for more
information,
Zone #97: Polling Loop Short: Monitors the polbng loop wiring
for short circuit
faults, See the POLLING
LOOP section for more information.
Zone #99: Keypad Panic: Activated by simultaneous depression of the console
~] and [#] keys. See the KEYPAD FUNCTIONS section for more
information.