POWRING AND The 5140XM suppods, independent of auxiliary power considerations, up to
WIRING
sixteen 5137AD/51 37ADR mnsoles. The 5140XM can supply up to 1 amp of
euxitiaw standby power for consoles, pelting loop devices, motion detectors, 4-
wire smke detecfom, etc. (the maximum auxiliary standby bad that mn be drawn
is hinted by the capaciy of the backup battery
used. A 1 amp load requires a t
AH battery. See the POWERING THE SYSTEM section for more informat~).
Provided that the maximum permissible standby load is not exceeded, up to 11
consoles (at 90mA per wnsole) can be powered from the pane~s auxifiary power
1 and auxihary power 2 outputs.
Keep this in mind when adding consoles so that
the pane~s power supply is not overloaded resulting in a battery which does not
properly charge.
If the pane~s maximum permissible standby load is exceeded, then additional
mnsoles an~or other auxilia~ devices can be powered from a separate UL
Commercial Listed Wwer supply. The Alarm-Saf model AS/PS5-BFS-l 2-UL
Commercial Fire Listed supply can be used to power additional consoles and/or
other auxiliaw fire davices. The dia~ram below shows how to make connections
to the
Alarm
-Saf power supply. -
R,ure 2. MM -SW POWER SUPPLY CONNE~ON DIAGWM
Supplementary consoles may be wired to a single wire run or individual consoles
may be mnnacfed to separate wire
rims. The maximum wire run length from the
panel
to a mnsole whwh is homrun back to the panel must not exceed:
CONSOLE WIRE RUN
. ------ .“
F
LtNU I nZ
,#,6*1 gaugewn)
If more than one console is wired to a single
run, then the a~ve maximum lengths must
be
divided by the number of consoles on
the run (i.e. the maximum length would be
225 feet if two consoles are wired on a #22
NOTE: The length of all wire runs mmbined must not exceed 2000 feet when
unshielded quad mnducfor cable is used (1000 feet ff shielded cable is used.)
ADDRESSABLE
The 5137AD and 5137ADR mnwles are addressable devices. They have a built-
CONSOLE DIP SWITCH
in DIP switch which is used to select their operating address. Each console used
SETTINGS
must be assigned a unique address for proper system operation. Refer 10 the
figure and table below to set this DIP swtch. The panel can be programmed to tell
it what sounding options should be used for each console (refer to DEVICE
PROGRAMMING in the PROGRAMMING THE SYSTEM section for more
information). The pane~s standard factory default enables all console addresses
and sets each console for no sounder suppression. You only need to use the
Device Programming Mode at initial installation if you desire to change ‘he
sounder options for one or more consoles.
-,,
NOTE: Some versions of the 5137AD/5137ADR mnsoles have a sixth DIP
swich. Make sure that fhe sixth swtch is in the DOWN psifion.
-14–