X. REGULATORY AGENCY REQUIREMENTS
NOTE 1: Set field 3’82 to “O” to disable burglary faatures H
burglary protetiion
will not be installed (disables
AWAY, STAY, MAXIMUM, INSTANT, TEST and
CHIME key fundions).
NOE2 Thasdb”ns in brackets []pmvide more detailed
wiring and pr~ramming instrutiions.
NOK& For fire only or wmtination fire and burglary
installations, AC loss reports must retransmitted
to the central station batween 6 & 12 hours after
bss of AC pwer (field “19=2), and neither bell 1 or
bll 2 should ring an alarm 4 hours after bss of AC
power (fields ’18, 3.58=0). For burglary only
installations, AC loss must be transmitted less
than 6 hours after loss of power (field “19=0 or 1),
and etiher bll 1 or bell 2 should ring an alarm 4
hours after bs of pwer (fieti “18 or 3’58=1 ).
UL864/NFPA72A
Local Fire
.
CO flfigUrE at least one ball output for supewisbn and
wire polatized fire alarm indiato~ to it. Program this bell
for pulsed operation when burglary protection will be
installad [BELL OUTPUTS].
UL864/NFPA71
Central Station
. You may use a 7620ULF or 7920SE LORRAS
abne, tha
main dialer wkh the LORRA, or the main dialer with tha
5140DLM Ba&up Dialer Mdule. Refer to the LORRA
Installation Instrutiions for more detaiiad informatbn.
. When using the LORRA, mnneti its channel inputs to
the 5140XMS Fire Alarm, Fire Supewisory (if installad)
and Trouble Triggers. Also connad its XMIT OKAY
output to the 5140XWS J2/hr put 1 input. Program
J31nput 1 zona 73 for a 24 hour trouble response (type
19) to radb fauhs (ace TRIGGER OUTPUTS s~ion),
. When the main dialer is usad, enable it (field 3“30) and
rnnnea it to a telephone hne. Assign a 24 hour trouble
ras~rrse (type 19) to zone 74 to enable main dialer
supervision (field 3“1 O) (see DIALER OUTPUTS
sed”on). The 5140XM will advate the trouble trgger to
trip the LORRA If uaad) when tha main dialer is fauhad.
. When the 5140DLM Badup Dialer Modula is used, in~afl
h on tha 5140XMS PC board shield. Enable it (fieti 3“30)
and rnnned it to a separate telephone fine. Assign a 24
hour trouble response (type 19) to zone 75 to anable
backup dialer supervision (field 3.10) (see DIALER
OUTPUTS sedtin).
. When a dialer is used, program k to send fire alarm, firs
supewisory, trouble, AC loss and mmmunicator test
re~rts. Field .27 must be set to “024” (or less) so that
test reports are sent at least once eve~ 24 hours.
. if a sewndary phone number is programmed (field ’34)
then tha maximum number of dialer retries (field 3.21)
must ba restrided to 3, 4 or 5.
UL609
Grade A Local Mercantile Premises/Local
Mercantile Safe
and Vault
.
Confiiure one bell output for no supawision and wire a“
AB12 grade A beilhx to ti. Bell wires must be run in
mrrduit. Program ttis bell for steady alarm sounding, 16
or more minute timeout, and for tin formation of ar-ming
ding [BELL OUTPUTS].
. Attach a door tamper- switch (supphed) to the 5140XM
back-box. For safe and vault installations. a shock
sensor (not’supplied) must also be attachad tO the baA-
hx [MOUNTING THE CABINEm.
. Wir~ tha bell bx and 5140XM ~abinet tamper swkchas
(and shock sensor, if used) to zone 6. Select the zone 6
aiternate tamper furrtiion (field T 17=1) and assign zone
6 a day/night response.
. Entry dalays must not exceed 45 sewnds and exit
delays must not ex-ed 60 semnds.
. If 4190WH RPMs are used, set field .24 to “0” to enabl,-
tampar detedion. Saa the POLLING LOOP sedion for
notes regarding the usa of RPMs for montioting fire and
burglary sensors.
UL 365 Pollee
Station Connected Burglar Alarm
.
Follow the inafruaions for UL 609 local installations
For Grade A Service:
. You may use the main dialer alone, the main dialer with
the 5140DLM Back-up dialer module, the 7620ULF (or
772o) LORM alone or tha 346 plar~ reversal relay.
. When using the main dialer a[ona, program it to send
burglay alarm, low battery and communicator test
rapfis. Held ’27 must be set to ‘024” (or less) so that
test reports are sant at least onca every 24 hours.
. Whan using tha main dialer with the 5140DLM back-up
dialer mdule, assign a 24 hour trouble response (type
19) to zones 74 and 75 (field V1 O) to enable su~wision
for kth dialers. Proaram tha dialer to send burolaw
alarm, troubla and I;w battery reports (see DIA”LER
OUTPUTS =tion).
. When the 7620ULF (or 772o) LORRA or 346 polarity
reversal relay is used, connect it to the 5140XMS
burglary/audible panic atarm trigger (see TRIGGER
OUTPUTS setion).
For Grade AA Service:
. You may use a 7920SE LORRA alone or a 445 high line
security transmittal.
. Conned the 7920SE LORRA or the 445 transmitter to
Ihe 5140XMS burglary/audible panic alarm trigger (se
TRIGGER OUTPUTS sdion).
UL611/UL 1610 Cantral Station Burglar Alarm
. Follow the instructions for UL 609 local installations
For Grade A Sawice:
. ~yR~~ use the main dialer with the 7620ULF (or 772o)
. tinned the 7620ULPS inout channels to the 5140xMs
burgIary/audible panic alarm and trouble ttiggers. Also
connect the 7620ULPS ‘XMIT OK” outgut to the
5140XMS J21nput 1 input. Program J2/lnpui 1 zone 73
for a 24 hour trouble raspnse (type 19) to radio faults
(sac TRI=ER OUWUTS s~tion).
. Enable the main dialer (field 3.30) and conned it to as
telaphone line. Assign a 24 hour trouble res~nse (type
19) to zone 74 to enable main dialer supewision (field
3.1 0). Tha 5140XM will activate the trouble triaaer to ttio
the 7620ULF when the main dialer is fauked (s;; DIALER
OUTPUTS section).
. Program the dialer to send burglary alarm, trouble,
opening/cbsing and low battery re~tis.
For Grade AA Sawi~:
. Follow the instructions for Grade A installation excapt
use tha 7920SE in place of the 7620ULF.
New York City Requirements
New York City Fire Department
Drohibits commercial
combination {ire/burglary panel;. When using the
5140XM for fire prote~ion, burglary prot~tion cannot&
implemented.
-.