2. Fire Supervisory Response On Short Circuit Or Open Circuit Selection
(new program field 3*13)
Field 3*13 allows the installer to select whether a short circuit or open circuit fault will initiate a
supervisory response on zones programmed for fire supervisory response (response type 18).
3*13 0 = trouble on open / supervisory on short;
1 = supervisory on open / supervisory on short
When field 3*13 is set to "0" (default), zones programmed for fire supervisory response provide
trouble on open / supervisory on short. When field 3*13 is set to "1", zones programmed for fire
supervisory response provide supervisory on open / supervisory on short response.
3. Extended waterflow and fire supervisory delay (new program field 3*18)
Field 3*18 allows the fire waterflow (response type 17) and fire supervisory (response type 18) zone
delay programmed in field 3*16 to be extended.
3*18 0 = no extended delay; 1 = delay in 3*16 times 4
When field 3*18 is set to "0" (default), the delay programmed in field 3*16 applies. When field 3*18 is
set to "1" the delay programmed in field 3*16 is multiplied by 4 (allowing delays up to 120 seconds).
4. Manual/Automatic fire Waterflow alarm silencing (new program field 3*14)
Field 3*14 allows the installer to select whether zones programmed for fire waterflow response
(response type 17) can be silenced manually (security code + OFF) or can be silenced automatically
when waterflow ceases.
3*14 0 = manual silencing only; 1 = automatic silence when waterflow ceases
When field 3*14 is set to "0" (default), waterflow zones can be silenced manually only, by entering the
security code + OFF. When field 3*14 is set to "1", waterflow zones will silence automatically when
waterflow ceases (provided that no other fire alarms are present).
Note that if field 3*14 is set for "1", entering security + OFF will not silence waterflow alarms while
water continues to flow.
5. Clarification of Duress Trigger Operation
The Installation Instructions currently state that the silent panic/duress trigger goes HIGH when a
silent panic or duress alarm occurs, and remains high until the security code + OFF is entered. This is
true when a silent panic alarm is initiated via a hardwired or polling loop zone. However, if the duress
alarm is initiated via console key depression, the silent panic/duress trigger remains high for about 2
seconds only, then returns to the low state.
ALARM DEVICE MANUFACTURING CORPORATION
A DIVISION OF PITTWAY CORPORATION
165 Eileen Way, Syosset, New York 11791
Copyright © 1994 PITTWAY CORPORATION
N6019V1XX 12/94