IX. TESTING THE SYSTEM
BATTERY TEST When AC power is present, the 5140XM will mrr a brief battery test every 60
semnds to determine if there is a battery conneded, and will run an extended
battery test every 24 hours to check on the battery’s condition. If the 5140XI
fitis that the battery vokage is low (less than spprox. 11 .5V) during one of these
tests, it initiates a console ‘System LoBa~ display, a rapid console beeping
sound, and it sends a bw battery reprf to the central station of the dialer feature
is used). me console ~n be cleared by entering any security @de + OFF, and a
restore report will be sent to the central station after a subsequent test indicates
that the problem (diswnnecfed or low battery) has been wrrecfed.
DIALER TEST
The5140XM may be programmed to automatically transmit test re~tisto a
central station at intewals ranging from once par hour to once per 199 hours (field
‘27). ULrequires that a test reporfbs transmiffedat least once every 24 hours.
The 5140XM can be programmed to send the first re~rf at any time of the day, or
at any day of the week after ~wer up (field ’83)
FIRE DRILL TEST This test causes fire bells (or any bell hating a mrr-zero response type in field
(-de + [#]+ 69)
3’10) to be activated ~n either steady or pulsing manner as programmed in field
3’15) for the pu~se of mnducfing a fire drill or a bell test. This test can only be
activated by the installer, or a master user by entering the mrrespondng security
-e and pressing [#] +69 while the burglav Wrfion of the system is disarmed.
Consoles will dsplay “FIRE DRILL ACTIVP while this testis active. The test may
be stopped by entering any security code and pressing OFF. Note that the
system continues to monitor all 24 hour zones (fire, panic, etc.) while this test is
a~lve, and will end the test when an alarm condition is detected. This test should
be mnducted at periodic intervals as determined by the local authority having
jurisdiction.
ONE MU FIRE WALK
This test causea the system to sound console beeps and bell dings in resWnse
Teti (code+ [#] + 68) to fire zone fauks (zone type 9, 16 & 17) for the pu~se of allowing proper zone
operationto be checked without triggering alarms. Note that the System will n.,,
be operational as an alarm system ~.e. cannot sense alarms) while this test is’””
active. The test can only be activated by the installer by entering the installer’s
wde and pressing [#] + 66 while the burgla~ portion of the system is dsarmed.
This test shouti be anducted at periodic intewals as determined by the local
authority having jurisdiction.
When this test is first activated, the system will sound fire bells (or any bell hating
a non-zero res~nse type in field 3’1 O)for 3 seconds. The system will also send a
“Start of walk tesv message to the central station, and will tight all console
indicators and display window segments to verify that they are wo~ng properly.
The consoles will then display “Fire Walk Test in Progress” and will sound a single
beep every 15 seconds while this testis active.
Fauff and reset each fire alarm sensor in turn. Each action should cause consoles
to beep and fire bells (or any bell assigned to the sensor’s zone in fields 3’70-
3’61) to ding. The consoles will display the zone number and the associated
alpha descriptor while the zone remains fauffed. The system automatically issues
a smoke detector power reset about 10 seconds after it finds a fauh on one of
these zones, to
allow fauhed detectors to be reset.
The 4192CP, 4192SD & 4192SDT polhng loop smoke detectors can also be
tested by entering [#] + the detector’s 2-digit
ID (zone) number at the console. if a
valid detector number is entered, the consoles will beep and tire bells will ding.
The consoles will display the detector number for a few seconds. An invatid
detector number will be ignored.
To end the test, enter any security code and press OFF. An end of walk test
message will be sent to the central station. Note that the test will automatically end
if no fauns are detected within a 30 minute lime period.
–56–