Type 09
Supewiaed Fire (No
Verification)
,-.
Type 10
itierlor w/Delay
Type 16
Fire Mth Verification
Type 17
Fire Waterflow
Ty~ 18
Fire Supewiaory
Type 19
24 Hour Trouble
Used for zones containing smke detectors (when smoke alarm verification is not
desired), or containing heat detectors, pull stations, etc. An open in this
zonf? will
intiate a trouble
sig~l. A s~ti in this zone will mtiate afire alarm.
This zone type gives entry delay (usiW the programmed entry time), if tri[]ped
when the panel is amed in the Away rode. This zone type is also active
dlJfing
maximum mode, but no delay is provided (alarms occur immediately
if zone is
tripped). This zone type Is bypassed when the panel Is srmed in the
Stay or fnstant modes. Delay begins whenever sensors in this zone are
violated, regardless of whether or not an entry/exif delay zone was tripped first.
Used when smke alarm verification Is desired on hardwire and polling loop zones
mnfaining only 2-wire or 4-wire smoke detedors. An open will initiate a trc,uble
response and a short initiates a fire alarm res~nse, Initial short detection causes
6 second smoke detector power reset. Subsequent short detection wit~n 90
smnds of reset causes fire alarm.
An open in this zone causes a trouble response. Shorts which remain present for
bnger than the programmable time delay cause a fire alarm response,
This type is assigned to a zone haviW sensors which monitor fire sprinkler
systems ~.e. PIV switches, etc.). An own in this zone causes a trouble. Shofls
which remain present longer than the programmable time delay cause a
supervisory res~nse. Supervisory response will not activate a bell output,
An open or shoti in this zone causes a trouble response. No external alarm
sounders are actuated.
,-
-.7-