AUXILIARY RELAY
The 5140XM provides a built-in “Form C“ relay with contacts rated at 28
VACNDC, 2.8 amps max. This relay maybe programmed for one of the funcfbns
betow (field 3’61):
. Alarm Activation: Steady acfivatin in response to an alarm on one, some
or all zones as selected in fie~s 3’70 through 3’81. If field 361 is set to”1”,
the auxiliay relay remains asfivated until timeout (which is programmed
independent of the bell 1 and bell 2 timeouts; tieti 3’60) or until the 5eCurify
code + OFF has been entered. If field 3’61 is set to ‘4, the auxihary relay
remains activated until the installer or master mde + [#] +67 is entered.
When this functiin is used, the auxiha~ relay Hn be used for elevator recall or
ventilator shutdown on fire alarms or when wired to the aux power 1 output or
to a separate power supply (such as Alarm-Saf model AS/PS5-BFS-l 2-UL
see the REMOTE CONSOLES section), the auxiliary relay can be used to
provide a third (unsupewised) bell output for supplementa~ strobes,
sounders, etc. as irrdiiatad in the diagram, below. By defauk, the auxilia~f relay
is sef to acfiiafe on zone 1-8 alarms with no timeout (field 3“61 =1 ) as m“~hf W
required for a common fire and burglaV alarm strobe itilmtor usage.
When fieM 3’61=1, the auxiliary relay can also be programmed to give a brief
ativafion for confirmation of arming (field 757) or for errfry/exit or perimeter
zone fauks while CHIME me is active (fieti 759).
. Trouble/Supervisory Activation: Steady activation in response to any
zone or system related trouble co~tion or to any fire supervisory condiiin.
Remains activated until all fault conditions have been corrected and the
security de + OFF has been entered.
. 4-Wire Smoke Detector Reset: Momentary (6 second) activation at
second entry of OFF sequence wtich interrupts power to 4-wire smoke
detectors connected to hard-wired zones (zones 1-8) or to polfing tip zones,
allowing the detectors to be reset following an alarm. Power to 4-wire smoke
detectors should be wired to the auxitia~ relay and to the auxilia~ power 1
output as shown in the diagram bebw.
. Batte~ Savefi When ttis function is selected, the auxiha~ relay will normally
be activated ~.e. N.O. and pole contacts will be connected, N.C. confa~ will be
open) and will de-advate 4 hours after the stafi of an AC power failure. Using
this feature, noncritical toads (such as supplementary mnsoles) which do no
need to be supported for the full 24 hour baffeV backup period can be
disconnected from the auxitiary outputs, allowing a smaller capacity battery to
be used. The relay re-acfivates within a few seconds after AC power restores.
Rgure 5a. AUXILIARY REMY WIRING
(Shows how to wire A.. Relay for .nsupewisd, poweti
slam output.)
- ALARM
r/7
78910
11et2
AUX REMY
)
FACTORY DEFAULTS
.
. Activates for zones 1-8
~ : : :
0
alms (steady alm
: x
z
output)
n
2
;
. No t,meo”t
NOTES
/“ ;
. u.. no.-polatiz~
cAN DWW pOWERFROMWE AUX WR 1
i“ticati”g devices
OUTPUTORFROMSEPAWTE SUPPLY
. wring is not
..pemised
. Do not exceed !he
+-
raflngs of the SUPPIY
u=O. 17au. pwr 1
output used, then
c.mtined slam
c.ment drawn from
,“. pwr 1, a.x pwr 2,
bell 7 and bell 2
.a..ot ,xce&
2.3A mm.
figure 5b. AUXIL1~Y REWY WIRING
(Show how to ware.“, relay for 4-wire moke deltior wwer 1=.1)
I
I
&J
EOLR
.- 17 –