
2-WIRE POLLING LOOP EXPANSION (Zones 9-64)
GENERAL
INFORMATION
INTERCOM
INTERFERENCE
ADVISORIES
POLLING LOOP SMOKE
DETECTORS
The 5140XM provides a built-in 2-wire polling loop interface which allows the
number of zones to be expanded from the basic 8 zones to UPto ~ zones u.sin9
various addressable polfing loop sensors. The panel supewises the ~lhn~ \p
wiring for open, short and earth ground faufts. See below for a fist of comptile
sensors and for comments regarding reefritions on burglary and fire usage.
The potting loop provides power to sensors and serves as a mmmunication path
between fhe panel and sensors. Each sensor must be assigned a unique
address ID number (from 9-64) before being connected to the polfing loop. Most
sensors have DIP switches for this purpose. See the DIP SWITCH SETTING
TABLE FOR POLLING LOOP DEVICES for information on how to assign ID
numbers using DIP switches. Care must be taken to assign unique ID numbers to
each sensor in order to allow the panel to supervise and provide unique wnsole
sfatus indications for individual sensors.
Sensors can be connected to a single run, or groups of sensors may be
connected fo separate wire runs without affefing the pane~s atifity to supervise
individual senmrs. Follow the wiring instmcfions provided with individual sensors
(4190WH wiring diagram is provided at the end of this manual). Be sure to
observe sensor polarify when wiring. The maximum allowable wire run length
between the panel and the last sen~r on a given wire wn is as follows:
Pollin Loo Wire Run Lengths
=
NOTE: Twisted pair remmmetied for all normal wire runs.
IMPORTANT: The maximum comtined polfing loop run is 400V. If using
shielded wire, the maximum is 2000. If longer wire runs are needed, a 4197 Loop
Extender Module must be used.
If an intercom system is being used, the ~lhng loop wires must be as far frorn%he
intercom wiring as possible (minimum 6). If this spacing cannot be achieved,
shielded wire must be used. If this is not done, interference on the intercom
system might occur. Also note that the maximum total wire length sup~rted is cut
in hati when shielded wire is used.
The maximum allowable current draw on the polhng loop is 84mA. Refer to the
POLLING LOOP CURRENT DRAW WORKSHEET (found in the POWERING THE
SYSTEM section) for current draws of various Wlfing loop devices. If more than
64mA is being drawn, use of the 4197 provides another loop with 64mA
avdlable.
Make certain to include the total current drawn on the pelting loop in the Total
Standby/Alarm Load Worksheet (see POWERING THE SYSTEM section) when
figuring the total auxihary load on the pane~s power supply.
Can be added to the 2-wire Poling Loop on zones 9 through 84 (as programmed
in fields ’03, ’04, ’05, 1’01, 1’02, 1.03, 1’04 and 1.05). These detectors have a
buiti-in RPM which is DIP switch programmable. They are wired in parallel to the
pelting loop, and do not need auxikay power or a separate reset switch. The
polfing loop provides power and reset signals to the detectors, as well as alarm
and frouble signals from the detectors.
4192SD Photoelectric Polling Loop Smoke Detector
Direct wire photoelectric smoke detector wifh built-in RPM which is DIP switch
programmable.
4192SDT Photoelectric Polling Loop Smoke Detector w/Heat
Detector
Direct wire photoelectric smoke’ detector with f 35°F (57°C) heat detector, and
buiti-in RPM which is DIP switch programmable.
4192CP Ionization Smoke Detector
w
DireCl wire products of combustion ionization detector with buik.in RPM which is
DIP switch programmable.
-1o-
Comentarios a estos manuales