III. PERIPHEWL DEVICES
F.,
GENERAL
INFORMATION
TWO CONSOLE PORTS
REMOTE CONSOLES
The 5140XM panel interfaces to 5137AD (gray bezel) and 5137ADR (red bezel)
alpha custom LCD consoles. These consoles provide visual and audible
indication of system status and allow the user to enter system operating
commands. These consoles provide the following features:
. 2-fine, 32 character(16 characters per hne) alpha numeric LCD display wtich
provides a programmable “Enghsh Language” description for each zone.
. 12 key telephone style keypad. The keys are back-~i.
. Built-in sounder which provides audible indications of alarm, fire supervisory
and trouble conditions.
. Choice of gray or red front bezel.
NOTE: Many municipa~ties require that fire system annunciators be red in color,
Check wlh the authodfy having jurisdiction before choosing a console color for
your installation.
. 90 mA current draw.
The 5140XM provides 2 console interface Pfls. Port 1 uses terminals 11.14 on
the main PCB terminal block and port 2 usee pins 1,4,5,, 7 on the main PCB J4
connector as indicated below. The wrt 2 ~wer/data wires are elecfricallv isolated
from (i.e. not affected by open, short or earth ground faults on) wrt 1 ~wer/data
wires. Note that the 4142TR nine wire cable (1 cable suppfied) is used to m:ike
connections to the J4 connector.
Port 1
terminal 11: aux power#l output (to mnaole red wire)
terminal 12: ground (to mnsole black wire)
terminal 13: data in 1 (to console green wire)
terminal 14: data out 1 (to console yellow wire)
Port 2
J4/pin 1: ground (to console black wire)
J4/pin 4: data in 2 (to mnsole green wire)
J4/pin 5: aux power W output (to console red wire)
J4/pin 7: data out 2 (to console yellow wire)
When only 1 console will be used in the installation, this console must be
mounted on or near the cahnet (see the MOUNTING THE CONSOLES section)
and may be wired to either wrt. When more than 1 console will b installed, the
“main” console must be mounted on or near the caMnet and must be wired to
Pod 2. The “suppleme~ary” consoles can be mounted where desired and must
be wired to Port 1. The “main” console will continue to function even when
wiring
faults prevent the “supplemental” consolee from operating properly, Note that
the panel can detect earth ground faults on Port 1 and 2 wiring but does not
supewise this wiring
for open and short circuit faults.