FIRE SUPERVISORY AND TROUBLE
GENERAL
INFORMATION
SUPV & “CHECK”
MESSAGES
OTHER TROUBLE
CONDITIONS
POWER FAILURE
The word “SUPWont heconsole’sd isplay accompanied bya rapid beeping,
indicatee that afire supewisory condition exists. The word “CHECK on tb””
Console’sdisDlav. accompanied bvaraDid “beeDina’’a ttheConsole.i ndicatet-’
that there is a tr~uble condfion in tfie system. The a~dible warning sound can be
silenced by pressing any key.
. A display of “SUPWaccompaniedbya sensor zone number (l-64) andan
alpha descriptor (if programmed) indicates that a fire supervisory condition
exists on that zone which can compromise the operation of the fire alarm
system. lnstmct theuserto CALL FOR SERVICE immediately.
. Adisplay of''CHECK accompanied byasensor zone number (l-W) andan
alpha descriptor (if programmed) indicates that aproblem exists onthat zone,
The user should first, determine ifihe zone(s) displayed are intaci and make
ihemso iftheyare noi. Theuser should then enter asecurtiy code and press
OFF to clear the display. Instinct the user to CALL FOR SERVICE immediately if
the display does not clear.
. Adisplay of theword ''CHECK acmmpanied byasystemzone number (7O-99)
and an alpha descriptor (if programmed) indicates that a problem exists with the
system wtich can compromise system operation. Instruct the user to CALL
FOR SERVICE immtiately,
. Adisplay of''COMM. FAILURE atthe Console in@caies ihaiafailure occurred
in the telephone communication portion of your system. Instruct the user to
CALL FOR SERVICE immediately.
. Adisplay of''SYSTEM LO BA7indcates ihaialow batie~@ndtion exisiswith
the system’s backup battery. Instruct the user to CALL FOR SERVICE
immediately.
If the POWER indicator is off, and the message “AC LOSS is dsplayed, the
system is operating on battery backup power only. Instruct the user to CALL FOR.=
SERVICE immediately if AC power cannot be restored.
As shipped, the panel is pre-programmed (field’19) to send an AC loss report to
the central station between 6 and 12 hours after the loss of power. The actual
time of transmission within this interval is random so as not to simultaneously flood
the central station with reports from many panels installed in the area of Wwer
outage. (UL requires this setting for field’19 for commercial fire installations.)