BELL CIRCUIT OUTPUTS
GENERAL The 5140XM provides two ball circuit outputs for operating fire and burglary alarm
INFORMATION
indicating devices (belll -terminals 3,4andbe112 -terminals 5,6). Each oulouf
may be independently selected for the following features:
.,
.
.
.
.
.
class B (style Y) supervision (used for fire bell circuits) using a 2K EOL resi~-or
(model 610-7, supphed) or m supervision (used for burglary bell circuts).
System zone 70 monitors the supewision status of the bell 1 output and
system zone 71 monitors the supewision status of the bell 2 output. The
pane~s response to fauks on these outputs is determined by the zone type
programmed in field 3’10 for the wrrespanding system zone.
NOTE: Cutthewhite~mper Wl (W4)onthe main PCBandprogram zone70
(zone 71) for no res~nse to disable supervision for bell 1 (bell 2). No EOLR
required.
activation by alarm candtions on one, some or all protection zones (fieWs 3’70
through 3’61)
short ding for canfirmtion of arming (field’16 for bell 1, 3“57 for ball 2) and for
entry/exif or perimeter zone fauks while CHIME mode is active (field 1.47 for
bell 1,3’59 for bell 2)
activation in a steady or pulsing manner in response to alarm candfiion (field
3’1 5)
2 to 30 minute timeout or no timeout (field’ 13 for bell 1,3’60 for bell 2). Note:
burglary bell circuits must be programmed for 16 (or more) minute timeout.
POWR AND WRING
Each bell outpuf is rated as follows: 10VDC 14VDC, 2.3 amps max., pwer
Umited. Note that the total alarm mrrent drawn from the aux power 1, aux power 2,
bell 1 and bell 2 outputs cannot exceed 2.3 amps for battery independent
operation.
By default, bell 1 is set to operate as an unsupewised burglary ball output. You
may use any UL hsted, non-palafized burg laW indicating device rated for 10-14
VDC operation on this output. Note that a local burglary grade A tisting reqt :
that a bell in a tamper protected housing be used (such as the Adem A=)
and that bell wiring be run in conduit. By defauk, bell 2 is set to operate as a
supervised fire bell output. Note that the panel supervises this wiring for open,
shod and earth ground fauks. You may use any UL fisted, polarized fire indiiati~
device rated for 10-14 VDC operation on this output. Observe polarity when
wiring polarized devices. Some examples of mmpafible devices are given babw.
The diaaram shows how to make connections to these outputs.
Exampl;s of Compatible Alarm indicating Devices
Burglary
Bells AdemwAB12
(9
rade A bel~housing)
Fire
Bells AdemmWFP8-12 (W bell)
Ademm WFP1O-12 (10” bell)
Horns
System Sensor PA400R (red piezo horn)
System Sensor MA-1224 (red horn)
System Sensor MAfSS-12 (horn and strobe)
Strobes
System Sensor SS-12
–16–
~g”re 4. BELL CIRCUIT WIRING
(Shows wiring for bell o.tp.t* configured using fadow
default programming selections)
.m
BELL 1 FACTORY DEFAULTS 3 4 5 6
~: ;i~~flg.red .S a b“’gtav
. use non-polarized Gmde A
indcating devices leg Ademco +
+-
N.. AB12 see below)
BELL;
BELL 2
. Wiring is not s“pewlsed ...!
whhtejumper, W?, on mat. PCB
. Activates for ,.”,s 3.8 .[am.
. Steady al.m .utPut
. 16 minute timmut
BELL z FACTORY DEFAUL=
Bell 2 is con fig”,ed as a fir. bet!
.,,.,,,,
“,. ”...
.
Us. Wlatized Indicat,”g
12~::LRl
devices
. C!ass B oDen/shofl supewisio”
(M:=~
.24 h, trouble cesPo”* tO f~UltS
. Activates for .0”, 1, 2 .l.ms
. Pulsed alarm outPut
. No timeout
AS32 BELWBOX WIRING
hBt 2 WIRING NO=S
. D,sco””mt the ml 2S
fati.v wires .o”.mNo”
“al #4 to K
. ...
. Zone 6 should be
Programmti f.r a day
tw.blelnight slam (qpe
or 24 hour slam (WPe07
response
. w,,, Pa”el, s door tamw
switch in series with z..
. AII wiring from AB12 to
~o;yt be W. in