1-1
SECTION 1
General Description
••••••••••••••••••••••••••••••••••••••••••••••••••
About the VISTA-128BP/VISTA-250BP
The VISTA-128BP/VISTA-250BP is an 8-partition, UL Listed control panel with the following features:
•
Up to 128 zones for VISTA-128BP; 250 zones for VISTA-250BP (hardwired, polling loop, and wireless zones)
•
Up to 150 user codes for VISTA-128BP; 250 user codes for VISTA-250BP
•
Supervision of bells, keypads, RF receivers, and output devices
•
Scheduling capabilities (allows certain operations to be automated)
•
The capability to link up to 8 control panels using Panel Linking Modules
The VISTA-128BP/VISTA-250BP can interface with the following devices:
•
TeleSmart (See the TeleSmart instructions for operating procedures)
•
An alpha numeric paging device (VA8201)
•
Symphony (AUI)
•
Panel Link Module (VA8200)
•
An ECP Long Range Radio that can send Contact ID messages
•
An access control system by using either the ADEMCO PassPoint system (via the VISTA Gateway Module) or a
VistaKey module (via the polling loop)
U
L
The access control function is not Listed for use with the VISTA-128BP/VISTA-250BP Control Panel in a UL
installation.
The system supports either the VistaKey or the VISTA Gateway Module, not both.
NOTE: All references in this manual for number of zones, number of user codes, number of access cards,
and the event log capacity, use the VISTA-250BP’s features. The following table lists the differences
between the VISTA-128BP and the VISTA-250BP control panels. All other features are identical, except for
the Remote Keypad Sounder (field 1
✴
46 option 2), which is available only in the VISTA128BP.
Feature VISTA-128BP VISTA-250BP
Number of Zones 128 250
Number of User Codes 150 250
Number of Access Cards 250 500
Event Log Capacity 512 1000
Features
Hardwire and Optional Expansion Zones
•
Provides 9 hardwire zones.
•
Supports up to 16 2-wire smoke detectors on zone 1.
•
Automatically resets 4-wire smoke detectors using the J7 output when a code + off is entered.
•
Triggers the built-in sounders on other hardwired smoke detectors if one smoke detector annunciates an alarm.
This feature requires a 4204 Relay Module and/or the 333PRM.
•
Provides tamper supervision on the hardwire zones.