
VISTA-128BP/VISTA-250BP Installation and Setup Guide
5-8
FIELD
TITLE and DATA ENTRIES EXPLANATION
Exit Error Logic Enable
0
= disable
1
= enable
Exit Error Logic functions as follows: the system at the end of the exit
delay, if a door is left open or an interior zone is faulted, starts the entry
delay period, and sounds the bell(s), siren(s), and keypad sounders for the
duration of entry delay. This gives the user time to re-enter the premises
and disarm the system before exit error occurs.
If the user does not re-enter the premises and disarm the system, the
system bypasses the faulted entry/exit and/or interior zone(s). The rest of
the system is armed. In addition, the following dialer reports are sent to
the central station if programmed:
Exit Error by User (not sent when is using ADEMCO High Speed format)
Entry/Exit or Interior Alarm with the zone number
Bypass reports
U
L
Exit Error Logic is not suitable for use in a UL installation.
1*20
Exit Delay Reset
0
= disable
1
= enable
If enabled, when the panel is armed, the normal exit delay begins. After
the user exits, closes the door and then re-enters the premises, the exit
delay time is reset to the programmed value.
NOTES:
Exit Delay Reset is designed to allow an operator to re-enter the premises
to retrieve a forgotten item without triggering an alarm.
This feature may only be activated once after arming.
U
L
Exit Delay Reset is not suitable for use in a UL installation.
1*21
Cross-Zoning
U
L
Cross Zoning is not suitable for use in a UL installation.
Cross Zoning is designed so that a combination of two zones must be faulted within a 5-minute period of each other to
cause an alarm on either zone. This prevents momentary faults from one of the zones from causing an alarm condition.
You can select four "sets" of cross-zones (programmed in data fields 1*22, 1*23, 1*24, and 1*25), keeping in mind the
following:
•
Both zones in each set must protect the same area.
•
Both zones in each set must be in the same partition.
•
A fire zone must only be crossed to another fire zone protecting the same physical area
(see warning below).
DO NOT cross-zone a fire zone with a burglary zone under any circumstance. Cross a fire zone with another fire
zone only, and BOTH must be protecting the same physical area (no walls or partitions separating them). Consult
NFPA 72 standard for exact spacing requirements. We recommend that spacing between fire cross-zones be no
farther than 30 ft
.
Conditions That Affect Cross-Zone Operation
•
In the event of a continuous fault (lasting at least 5 minutes) on one of the paired zones, a fault on the second zone
causes an alarm immediately.
•
If one of the zones in a pair is bypassed or has a zone response type set to 0, the cross-zoning feature does not apply.
•
If an entry/exit zone is paired with an interior follower zone, be sure to enter the entry/exit zone as the first zone of
the pair. This ensures that the entry delay time is started before the follower zone is processed.
•
If a relay is programmed to activate on a fault of one of the zones, the relay activates without the other zone being
faulted.
Comentarios a estos manuales