Section 3 - Installing the Control
3-29
Panel Earth Ground Connections
In order for the lightning transient protective devices in
this product to be effective, the designated earth ground
terminal (terminal 30) must be terminated in a good
earth ground. Recommended wire gauge for the ground
connection is #16 AWG, run no farther than 30 feet.
The following are examples of good earth grounds
available at most installations:
• Metal Cold Water Pipe:
Use a noncorrosive
metal strap (copper is recommended) firmly
secured to the pipe to which the ground lead is
electrically connected and secured.
• AC Power Outlet Ground:
Available from 3-
prong, 120VAC, power outlets only. To test the
integrity of the ground terminal, use a three-wire
circuit tester with neon lamp indicators, such as
the UL-Listed Ideal Model 61-035, or equivalent,
available at most electrical supply stores.
The panel requires the earth ground
connection for its lightning transient protection
devices.
Determining the Control’s Power Supply Load
Use the tables that follow to calculate the total current
for the Auxiliary Power, the Alarm Output, and the
Polling Loop. In each table, multiply each device’s
standby and/or alarm current by the number of units
used.
1. In Table 1, enter devices used on the polling loop.
Calculate total current draw on the polling loop.
Table 1: Total Polling Loop Current Draw
Polling Loop Device Current # of Units Total
Polling Loop Subtotal
(terminals 24 & 25 – 128mA)
✳
✳
The total current cannot exceed 128mA. If total load exceeds
128mA, then a 4297 Loop Extender Module can be used. This
module is powered from the panel’s auxiliary power, and
provides a separate polling loop output, which can support an
additional 128mA load. Note that the total number of points
connected to the panel cannot exceed 119.
2. In Table 2, enter devices used on Auxiliary Power.
Calculate standby and alarm currents, then add to
get Auxiliary Power current subtotal.
Table 2: Auxiliary Power Current Load
Total Current
Device
Model #
Device Current X
# of Units
Standby
Alarm
Auxiliary Power Subtotal
(terminals 6 & 7 – 750mA max.)