VISTA-128BP/VISTA-250BP Installation and Setup Guide
3-26
If the phone plug is disconnected from the
control, the premise’s phones will not operate.
NOTES:
•
When the AAV indicates that the audio alarm
verification session is completed, all keypad sounds
are restored. Sirens are restored if the alarm
timeout period has not expired.
•
As part of its fail-safe software, the control limits
all audio alarm verification sessions to 15 minutes.
This is because once the session begins, the AAV
Module controls the duration.
•
If a new
Fire alarm
should occur during a session,
the control breaks the phone connection and sends
the new Fire Alarm report, then re-triggers the
AAV Mode. All other dialer messages triggered
during ongoing conversation are held until either
the AAV Module signals that it is inactive, or the
15-minute timeout occurs.
CONTROL/
DIALER HEADER
NOTE:
REFER TO AAV MODULE
INSTRUCTIONS FOR
CONNECTIONS TO AUDIO
SPEAKERS AND MICROPHONE.
•
•
•
•
•
EAGLE
1250
6
7
16
17
27
26
28 29
30
}
ZONE 5
(–)
(+)
(–)(+)
•
•
•
•
•
•
•
•
J7
DIP Switch
1 2 3 4 5 6
ON
CONTROL
EARTH
GROUND
RED (R)
GREEN (T)
GREY (R)
BROWN (T)
INCOMING
PHONE LINE
RJ31X
(–) EDGE TRIGGER (YELLOW)
PIN 3
SYSTEM POWER (RED)
SYSTEM GROUND (BROWN)
BROWN (–)
RED (+)
TIP
RING
EAGLE
SUPPLIED
CABLE
➤
➤
DIODE FROM
EOLR PACKAGE
TO PREMISES
HANDSET
Figure 3-35: AAV Connections to J7 Trigger
CONTROL/
DIALER HEADER
NOTE:
REFER TO AAV MODULE
INSTRUCTIONS FOR
CONNECTIONS TO AUDIO
SPEAKERS AND MICROPHONE.
•
•
•
•
•
EAGLE
1250
6
7
16
17
27
26
28 29
30
}
ZONE 5
(–)
(+)
•
•
•
•
•
•
•
•
J7
DIP Switch
1 2 3 4 5 6
ON
CONTROL
EARTH
GROUND
RED (R)
GREEN (T)
GREY (R)
BROWN (T)
INCOMING
PHONE LINE
RJ31X
YELLOW
RED
BROWN
BROWN (–)
RED (+)
TIP
RING
EAGLE
SUPPLIED
CABLE
➤
➤
13
14
15
16
V+
GND
4204
RELAY 1
SHOWN
OFF
NO
NC C
TO PREMISES
HANDSET
Figure 3-36: AAV Connections to 4204 Relay
Module
CONTROL/
DIALER HEADER
NOTE:
REFER TO AAV MODULE
INSTRUCTIONS FOR
CONNECTIONS TO AUDIO
SPEAKERS AND MICROPHONE.
•
•
•
•
•
EAGLE
1250
6
7
16
17
27
26
28 29
30
}
ZONE 5
(–)
(+)
(–)(+)
•
•
•
•
•
•
•
•
J7
DIP Switch
1 2 3 4 5 6
ON
CONTROL
EARTH
GROUND
RED (R)
GREEN (T)
RJ31X
(–) EDGE TRIGGER (YELLOW)
PIN 3
SYSTEM POWER (RED)
SYSTEM GROUND (BROWN)
BROWN (–)
RED (+)
TIP
RING
EAGLE
SUPPLIED
CABLE
➤
➤
4286
4 3 2 1
BROWN (T)
TO PREMISES
HANDSET
GREY (R)
INCOMING
PHONE
LINE
DIODE FROM
EOLR PACKAGE
Figure 3-37: AAV and 4286 VIP Module
Connections to the J7 Trigger
Installing TeleSmart
The TeleSmart system provides a telephone interface
and message center for an ADEMCO security system. It
has the following features:
•
4 unique mailboxes for storing messages
•
6 user access codes
•
Security system interface
•
Memo feature for leaving messages for other users
•
Caller ID capabilities for up to 25 phone numbers
•
Memory (speed) dialing for up to 15 phone numbers
•
Repeat dialing (automatically redials busy
numbers)
•
Last number redial
•
Call screening (with and without Caller ID)
•
Privacy (turns off the ringer)
•
Remote access of TeleSmart and security system
NOTE:
The keypad connected to the TeleSmart module
must be the 6139T.
U
L
TeleSmart is not permitted in UL installations.
Mounting the Telesmart Module
The TeleSmart Module should be mounted in the
security system’s control cabinet if space is available, or
within a grounded metal enclosure to provide proper
ESD protection.
Mounting Inside the Control’s Cabinet:
Use
double-sided tape to attach the module to the interior
surface of the cabinet, or hang it on two screws. Do not
mount it on the cabinet door or attach it to the control’s
PC board.
Mounting Outside the Cabinet:
Use the screw
holes at the rear of the module. Wires can be brought
out from the side or back (use the round breakout on
the back).
Affix the Summary of Connections label to the module’s
inside cover or to the inside of the cabinet door.