VISTA-128BP/VISTA-250BP Installation and Setup Guide
5-2
FIELD
TITLE and DATA ENTRIES EXPLANATION
*10
Exit Delay #1 (partition-specific)
Enter
03-15
multiplied by 15 seconds.
00
= no delay.
Exit delay defines the delay period that allows users to leave the premises
through a door that has been programmed as an entry/exit delay door
after arming the system without setting off the alarm.
*11
Entry Delay #2 (partition-specific)
Enter
02-15
multiplied by 15 seconds.
00
= no delay.
Entry Delay #2 is used for a secondary door requiring a longer delay than
those assigned to Entry Delay #1.
This delay may not exceed 45 seconds for UL installations.
*12
Exit Delay #2 (partition-specific)
Enter
03-15
multiplied by 15 seconds.
00
= no delay.
Exit Delay #2 is used for a secondary door requiring a longer delay than
those assigned to Exit Delay #1.
This delay may not exceed 60 seconds for UL installations.
*13
Alarm Sounder Duration
(partition-specific)
Enter
01-15
multiplied by 2 minutes.
00
= no timeout.
Defines the length of time the Bell Output and the keypads sounder will
sound for all audible alarms.
Must be a minimum of 16 minutes for UL installations.
Burglary or RS232 Input
0
= burglary
1
= RS232 input
If enabled, sets terminal 23 (high side (+) of zone 9) as an RS232 input.
This enables the system to receive serial data (75 baud) via terminal 23.
U
L
Using the RS232 input for automation is not permitted in UL installations.
*14
*15
Keyswitch Assignment
Enter
1-8
partition keyswitch is being used.
Enter
0
if the keyswitch is not used.
The keyswitch requires the use of zone 7 wired loop (zone 7 is no longer
available as protection zone). The fire and panic alarm voltage triggers
(J7) automatically become ARMING and READY status outputs for the
Keyswitch LEDs.
Openings/closing report as user 0” if enabled in field *40.
*16
Confirmation of Arming Ding
(partition-specific)
0
= disable
1
= enable
If enabled, produces ½-second external alarm sounding (ding) at the end
of exit delay (or after kissoff from the central station, if sending closing
reports).
Must be 1 for UL installations.
*17
AC Loss Keypad Sounding
0
= disable
1
= enable
If enabled, sounding at the keypad (rapid beeping) occurs when AC power
is lost (sounding occurs about 2 minutes after actual AC loss).
*19
Randomize AC Loss Report
0
= disable
1
= enable
If enabled, randomizes AC loss reporting between 10 and 40 min. after an
actual AC loss.
If disabled, AC loss reporting about 2 minutes after actual AC loss.
Selecting this option helps prevent an overload of AC loss messages at the
central station during a community blackout.
*20
VIP Module Phone Code
1-9
= first digit of access code
or
#
= second digit of access code (enter #
+11 for
, or # +12 for #)
To disable enter
00
for the 1
st
digit
If a 4285/4286 Voice Module is being used, enter the 2-digit phone code
used to access the system.
Must be disabled for UL installations.
*21
Prevent Fire Timeout
0
= disable (timeout)
1
= enable (no timeout)
If enabled, there is no timeout of the alarm sounder duration for all fire
zones, regardless of partition, so that fire sounding continues until the
system is reset.
If disabled, (timeout) the normal burglary sounder duration (field
13)
applies to fire alarms.