VISTA-128BP/VISTA-250BP Installation and Setup Guide
3-14
Installing Output Devices
The VISTA-128BP/VISTA-250BP support up to 96
outputs. Each device must be programmed as to how to
act (ACTION), when to activate (START), and when to
deactivate (STOP). The 4204, 4204CF, FSA-8, FSA-24,
4140SN and/or Powerline Carrier devices may be used
as output devices.
Installing the 4204 and 4204CF Relay Modules
Each 4204 module provides 4 relays with Form C
(normally open and normally closed) contacts. Each
4204CF module adds two style Y supervised bell
outputs to the system. For 4204CF modules, only
relays 1 and 3 on each module can be programmed.
The relay module will not operate until the
device address you have set the DIP switches
for is enabled in the control’s
Device
Programming
in the
#93 Menu Mode
.
To install the relay modules, see
Figures 3-21
and
3-22
and
perform the following steps:
Step Action
1 Set the 4204 or 4204CF’s DIP switches for a
device address
01-15
.
Do not use an address being used by another
device (keypads, RF receivers, etc.).
2 Mount the 4204 and 4204CF Modules per the
instructions provided with them.
Connect the module’s wire harness to the
control (6, 7, 8, and 9). Plug the connector
(other end of harness) to the module.
If you are mounting remotely, homerun each
module to the control. The table below shows
the maximum wire run lengths. Refer to the
instructions provided with the 4204CF for its
maximum permissible wire lengths.
Wire Gauge Maximum Length
#22 125 feet
#20 200 feet
#18 300 feet
#16 500 feet
3
SWITCH 4204 ADDRESS SETTINGS
POSITION ("—" means "OFF")
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
2
ON — ON — ON — ON — ON — ON — ON — ON —
3
ON ON ——ON ON ——ON ON ——ON ON ——
4
ON ON ON ON ————ON ON ON ON ————
5
ON ON ON ON ON ON ON ON ————————
ON
12345
➞
➞
➞
➞
➞
13 14 15 16
C
NC
NO
OFF
➞
ON
➞
DIP SWITCH
FOR SETTING DEVICE ADDRESS
AND ENABLING/DISABLING TAMPER
➞➞
COVER TAMPER (REED) SWITCH
➞➞
TB1
4204
TB2
4-PIN CONSOLE PLUG
➞➞
121110987654321
C
NC
NO
C
NC
NO
C
NC
NO
▲
RELAY
3
RELAY
2
RELAY
1
RELAY
4
TYPICAL
(SHOWN "OFF")
EITHER OR BOTH
CAN BE USED
➞➞
➞➞
DATA IN
FROM CONTROL
(–) GROUND
DATA OUT
TO CONTROL
(+) 12V
YEL
BLK
GRN
RED
Figure 3-21: 4204 Relay Module
SWITCH 4204CF ADDRESS SETTINGS
POSITION ("—" means "OFF")
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
2
ON — ON — ON — ON — ON — ON — ON — ON —
3
ON ON ——ON ON ——ON ON ——ON ON ——
4
ON ON ON ON ————ON ON ON ON —— ——
5
ON ON ON ON ON ON ON ON ————————
ON
12345
➞
➞
➞
➞
➞
OFF
➞
ON
➞
13 14 15 16
NC
NC
DIP SWITCH
FOR SETTING DEVICE
ADDRESS AND
ENABLING/DISABLING
TAMPER
➞➞
COVER TAMPER (REED) SWITCH
➞➞
TB1
TB2
4-PIN CONSOLE PLUG
➞➞
121110987654321
NC
NC
NC
NC
▲
EITHER OR BOTH
CAN BE USED
➞➞
➞➞
DATA IN
FROM CONTROL
(–) GROUND
DATA OUT
TO CONTROL
YEL
BLK
GRN
RED
(+) 12V; SUPPLIES POWER TO MODULE
CIRCUITRY (INCLUDING NOTIFICATION
APPLIANCE RELAY COILS). CURRENT
DRAIN AT 12V IS: 25 mA + (80 mA PER
ACTIVE OUTPUT)
NOTIFICATION APPLIANCE AND
CONSOLE DATA OUTPUTS ARE
POWER LIMITED
–
+
NOTIFICATION
APPLIANCE B
2K EOLR
#610-7
POLARIZED
NOTIFICATION
APPLIANCE
–
+
NOTIFICATION
APPLIANCE A
2K EOLR
#610-7
}
–
+
POWER FOR
NOTIFICATION APPLIANCE A,
NOTIFICATION APPLIANCE B
8-28VDC OR VFW. UP TO 2.4A
DEPENDING ON BELL CURRENT
- ALARM POLARITY
SHOWN
- EACH OUTPUT
PROVIDES
STYLE Y
SUPERVISION
- EACH OUTPUT
RATED 1.2A MAX
- USE
NOTIFICATION
APPLIANCES
COMPATIBLE
WITH
NOTIFICATION
APPLIANCE
POWER SUPPLY
VOLTAGE
RATING
Figure 3-22: 4204CF Relay Module
Installing the FSA Modules
The 8-zone LED Fire System Annunciator FSA-8 and
24-zone LED Fire System Annunciator FSA-24 enable a
fire response unit to identify quickly the point/zone of a
fire. These indicators may be used for other functions
as well, such as status indication. A maximum of 4 FSA
modules, in any combination, can be supported.
The FSA module will not operate until the
device address you have set the DIP switches
for is enabled in the control’s
Device
Programming
in the
#93 Menu Mode
.
To install the FSA module, refer to
Figure 3-23
and
perform the following steps:
Step Action
1 Set the FSA’s DIP switches for a device
address from 08 to 23. See the module’s
instructions for the DIP switch table.
Do not use an address being used by another
device (keypads, RF receivers, etc.).
2 Mount the FSA module horizontally to a
duplex box (quad box for FSA-24).
3 Connect the module to the control’s keypad
terminals (6, 7, 8, and 9).