
VISTA-128BP/VISTA-250BP Installation and Setup Guide
3-10
POLLING LOOP RATING:
128mA MAXIMUM
4192SD
SMOKE
4190
RPM
4278
PIR
23
21
22
+
-
POLLING LOOP
25
24
TO RIGHT LOOP
poll_loop-001-V0
Figure 3-16: Polling Loop Connections to the
VISTA-128BP/VISTA-250BP
Polling Loop Supervision
A short on the polling loop is indicated by a trouble on
zone 997 and reports as a trouble condition only. If
annunciation is desired, program the zone as type 05.
If a device on the polling loop fails (the panel cannot
"see" that device), the system displays a trouble
condition for all zones on that device. If the panel is
armed when a device fails, and the zone is a burglary
zone, the will go into alarm
A trouble on zone 997 prevents a partition from
being armed, unless all polling loop zones on
that partition are bypassed.
Using the 4297 Polling Loop Extender
The 4297 Polling Loop Extender may be used to provide
additional polling loop current, to extend the polling
loop wire run length, and/or to provide individual
electrically isolated polling loops. Refer to
Figures 3-17
and 3-18
, to follow.
DO NOT use the 4197 Polling Loop Extender
module with the VISTA-128BP/VISTA-250BP
.
Be sure to include the total current drawn on
the polling loop when figuring the total auxiliary
load on the panel’s power supply.
CONTROL PANEL
RPM
INPUT POLLING LOOP
EXTENSION POLLING LOOP
RPM
4297
RPM
RPM
TO
OTHER
RPMS
INPUT LOOP LIMITS:
EXTENSION POLLING LOOP LIMITS = SAME AS INPUT LOOP
•
128 mA MAX. LIMIT CURRENT TO 64mA ON ANY
INDIVIDUAL WIRE RUN.
•
NO MORE THAN 64 DEVICES MAY BE USED.
NO INDIVIDUAL WIRE RUN CAN EXCEED:
•
•
TOTAL LENGTH OF ALL WIRE RUNS COMBINED CANNOT
EXCEED 4000FT. (2000FT. IF USING UNSHIELDED WIRE
GAUGE LENGTH
#22 650 FT
#20 950 FT
#18 1500 FT
#16 2400 FT
• NO MORE THAN119 DEVICES COMBINED.
• TOTAL LENGTH OF ALL WIRE RUNS ON BOTH
LOOPS COMBINED CANNOT EXCEED 6400 FT.
(3200 FT. IF USING UNSHIELDED ). WIRE IN
CONDUIT, OR IF USING SHIELDED WIRE
polling_loop_003-V0
COMBINED INPUT AND EXTENSION LOOP LIMITS:
Figure 3-17: Polling Loop Connections Using One
4297 Extender Module
CONTROL PANEL
EXTENSION POLLING LOOP #1
4297
RPM
COMBINED INPUT AND EXTENSION LOOP LIMITS:
•
NO MORE THAN 119 DEVICES COMBINED ON THE INPUT LOOPAND EXTENSION
LOOP #1. NO MORE THAN 119 DEVICES COMBINED ON THE INPUT LOOP AND
EXTENSION LOOP #2.
• TOTAL LENGTH OF ALL WIRE RUNS ON THE INPUT LOOP AND EXTENSION LOOP #1
COMBINED CANNOT EXCEED 6400 FT. (3200 FT. IF USING UNSHIELDED WIRE IN
CONDUIT, OR SHIELDED WIRE). TOTAL LENGTH OF ALL WIRE RUNS ON THE INPUT
LOOP AND EXTENSION LOOP #2 COMBINED CANNOT EXCEED 6400 FT. (3200 FT. IF
USING UNSHIELDED WIRE IN CONDUIT, OR SHIELDED WIRE).
4297
RPM
INPUT POLLING LOOP
•
DO NOT CONNECT 4297 MODULES IN
SERIES (i.e., DO NOT CONNECT ONE
MODULE'S EXTENSION LOOP TO
ANOTHER MODULE'S INPUT LOOP.)
DO NOT CONNECT MORE THAN TWO
4297 MODULES IN PARALLEL.
•
polling_loop-004-V0
EXTENSION POLLING LOOP #2
Figure 3-18: Polling Loop Connections Using
Multiple Extender Modules
NOTE:
The input loop limits stated in
Figure 3-17
apply to
Figure 3-18
as well.
Wireless Zone Expansion
U
L
The 5881ENHC RF Receiver and the 5869 Holdup
Switch Transmitter are listed for UL Commercial
Burglary applications. All other RF receivers and
transmitters are not listed for UL Commercial
Burglary applications.
The following table lists the receivers that may be used
and the number of zones they support.
5800 Series Receivers
Receiver Zones
5881L up to 8
5881M up to 16
5881H up to 250
In Canada, 5800 systems must use 5882 Series
receivers: 5882L/5882H. Information to the 5881
Receivers applies as well to the 5882 Receivers.
Both receivers use the same transmitters.
RF System Operation and Supervision
The 5800 RF system operation has the following
characteristics:
•
The receiver responds to a frequency of 345MHz.
•
The receiver has a nominal range of 200 feet.
•
Supervised transmitters send a supervisory signal
every 70-90 minutes.
•
Zones 988 and 990 are used to supervise the RF
reception of receivers 2 and 1, respectively. The
reception is supervised for two conditions:
1. The receiver goes “deaf” (doesn’t hear from
any
transmitter) within a programmed interval of
time (defined by program field 1*30).
2. Proper RF reception is impeded (i.e., jamming
or other RF interference). The control checks
for this condition every 45 seconds.
Comentarios a estos manuales