VISTA-128BP/VISTA-250BP Installation and Setup Guide
4-10
Using an RF Transmitter Zone
A button type RF transmitter (5804) can be used to
provide access or egress for up to 4 doors. One button
will control one door. Also, a button can be used to
provide access or egress due to a panic or duress
condition.
An RF transmitter (5816) can be used with a remote
switch to provide exit in case of a fire alarm using a
PassPoint event action. To program the RF transmitter
for access control, perform the following steps:
Step Action
1 Enter Zone Programming in the #93 Menu
Mode.
2 Program the zone with a response type 27
(Access Point).
3 Enter the access point number (00-31) of the
door.
4 Indicate whether RF device is for entry or exit.
5 Enter the partition number
6 Enter the input type: button RF (05).
7 Enter the loop number.
8 Enroll the serial number
See Zone Programming in the Programming Guide for a
detailed explanation.
•
RF buttons and pendants must be assigned
to a user number in order to function. See
SECTION 9: User Access Codes
for the
procedure.
•
An RF transmitter will not provide access or
grant if the system is in any test mode.
Using Wireless Keypads
Wireless keypads (5827 & 5827BD) can provide another
way of entering or exiting the premises. They function
the same as alpha keypads, except when the code + #
73 is entered. This entry will allow momentary access
to ALL access points in the partition to which the
keypad is assigned To program the wireless keypad,
enter the partition the keypad is assigned to in field
1*48.
Control of Lighting and Appliances
Lighting and appliances can be controlled when an
access or exit event occurs. Lights or appliances can be
automatically turned on or off when a valid entry or
egress request is presented at an access point. To
control these devices, the VISTA-128BP/VISTA-250BP
relays or the ACS relays or triggers are used with
keypads and/or RF transmitters whose response type is
Access Point (27).
To program the control of lighting and appliances,
perform the following steps:
Step Action
1 Enter Output Programming in the #93 Menu
Mode.
2 Program all the information for the relay.
3 Select the output type: ECP (1) (4204/4204CF)
or (2) (X-10).
See Output Programming in the Programming Guide
for a detailed explanation.
Using the VISTA-128BP/VISTA-250BP for Stand-
Alone Access Control
The VISTA-128BP/VISTA-250BP can be used for access
control without interfacing to PassPoint ACS or
VistaKey. A user can trigger an access point (i.e., door
strike) for 2 seconds by entering User Code + [0].
To program the VISTA-128BP/VISTA-250BP for Stand-
Alone access control, perform the following steps:
Step Action
1 Enter Output Programming in the #93 Menu
Mode.
2 Program the output type as 1, or 2.
3 For type 1, program the ECP address and
relay number.
4 For type 2, program the house and unit codes.
5
Program the relay number in field 1
∗
76
(partition-specific).
See Output Programming in the Programming Guide
for a detailed explanation.
Programming for ECP Long Range Radio Programming for the Event Log
•
Program the LRR in
Device Programming
in the
#93 Menu Mode Programming.
•
Field ✳56: Selects the time the panel should wait
before it attempts to send a message to the second
destination..
•
Field ✳57: Select the initial reporting destination
for messages.
•
Field ✳58: Select events for the primary sub’s ID
•
Field ✳59: Select events for the secondary sub’s ID.
• 1
✳
70
Event Log Types (
1
=enable;
0
=disable for
each type)
• 1
✳
71
12/24-Hour Time Stamp Format (
0
=12 hr;
1
=24 hr)
• 1
✳
72
Event Log Printer On-line (
0
=disable;
1
=enable)
• 1
✳
73
Printer Baud Rate (
1
=300;
0
=1200)
• Event Log Report Codes
System Group #2 in the
#93 Menu Mode
.