Section 3 - Installing the Control
3-15
00000
ECP Bus
Dip Switch
Optional
Keyswitch
Connection
SIDE
VIEW
All Switches shown
in Up position.
(ECP Address 23)
Terminal
Block
Connect to
Keypad
Terminals
Figure 3-23: Wiring the FSA Module
Installing 4101SN Relay Modules
The 4101SN V-Plex Single Output Relay Module is a
serial number polling loop output device. The 4101SN
features the following:
Form C relay contacts rated at 2A, 28VAC/VDC
with contact supervision.
The position of the relay is supervised, but not
the actual external contact wiring.
One class B/style B EOLR-supervised auxiliary
input zone.
Operating power and communication with control
panels via the V-Plex polling loop.
Electronics mounted in a small plastic case with
tamper-protected cover.
Connect the device to the polling loop, terminals 24 (+)
and 25 (-). Be sure to observe polarity
Installing the 4300 Transformer
Powerline Carrier devices are controlled by signals sent
through the premises electrical wiring via a 4300
transformer. If you are using Powerline Carrier
devices, a 4300 transformer
must
be used in place of
the regular system transformer.
Powerline Carrier devices respond to on and off
commands sent from the panel through the 4300
transformer.
Powerline Carrier devices (such as X-10, ACT, Leviton)
are either plugged into standard AC outlets or wired
into the AC electrical system by a licensed electrician,
depending on the type of device used.
Note each devices House and Unit Code
setup, as these codes will be used to program
the devices in
Output Programming
in
#93
Menu Mode
described in the
Programming
Guide
.
To connect the 4300 transformer, see
Connecting the
Transformer,
later in this section.
Installing the Ground Start Module
U
L
The Ground Start Module is not intended for
use in UL Listed applications.
Output 1 may be used to trigger an optional 675
Ground Start Module for installations having telephone
lines that require ground start instead of loop start
operation to obtain a dial tone from the telco central
office.
When the panel has a message to transmit to the
central station, it seizes the line, goes off hook, and
then triggers the 675 Module to connect the RING side
of the telephone line to earth ground. The panel causes
the module to break the connection between RING and
earth ground when it obtains a dial tone.
To install the 675 Ground Start Module, perform the
following steps:
Step Action
1 Determine which side of the telephone line
is the RING side by connecting the (+) lead
of a DC voltmeter to earth ground, and the
(-) lead to one side of the telephone line.
The wire that reads + 50VDC is the
RING side.
2 Connect the 675 Ground Start Module to
the panels J7 connector trigger output 1, to
auxiliary power, and to the RING side of
the telephone line as shown in
Figure 3-24
.
3
Program field 1
46 Auxiliary Output
Enable with a [
0
].