Vista 120 Training Guide 40
4208 Hard Wired Expansion Cont.
• Press * to move to Report Code
• Press * (3 times) to move to Input Type
• Enter the Input Type as “06” Serial Number Polling Loop Device
• Press * to move to Smart Contact
• Leave as “0” (This is used for devices that monitor maintenance signals)
• Press * to move to V-Plex Relay
• Leave as “0” (This is used for Polling Loop Relays)
• Press * to move to Loop #
• Enter the Zone’s Loop Number (1 – 8)
• Press * to move to Learn S/N
• Enter Yes “1”
• Enter the 7 digit Serial Number applicable to that Zone or activate the Zone Concerned, or short Zone input
• Press * to move to Zone Summary
• Press * to move to enter next Zone Number
• Repeat above procedure until all required zones are configured, then Enter “000” & “*” at “Zone No.” prompt
to move to “Quit Menu Mode”.
• Enter 1 for Yes or 0 for no if more programming is required.
• The polling loop itself is a zone (997), and it has a default response type of 05, Trouble by Day/Alarm by
Night. No change is required.
• When programming is complete, enter * 9 9 to exit program mode.
For full system information and programming details refer to Vista-120a Installation & Setup Guide.