VISTA 120 PROGRAMMING FORM
Some fields are programmed for each partition (shown as shaded fields). See the PARTITION-SPECIFIC section for programming these
fields. Standard default (*97) values are shown in brackets [ ], otherwise default = 0.
*43 SUPPRESS RF SIREN ACTIVATION
[0]
FOR FIRE ALARMS 1= suppress wireless siren (e.g. 5840) activation on fire alarms
0= wireless siren sounds for fire alarms
*44 RING DETECTION COUNT
|
[00]
01-14; 15=answering machine/fax bypass; 00=no detection.
*45 PRIMARY FORMAT
[0]
0=Low Speed; 1=Contact ID; 2=Ademco Exp. High Speed; 3=Ademco Express
*46 LOW SPEED FORMAT (Primary) [0]
0=Ademco Low Speed; 1=Sescoa/Radionics
*47 SECONDARY FORMAT [0]
0=Low Speed; 1=Contact ID; 2=Ademco Exp. High Speed; 3=Ademco Express
*48 LOW SPEED FORMAT (Sec.) [0]
0=Ademco Low Speed; 1=Sescoa/Radionics
*49 CHECKSUM VERIFICATION [0] [0] Prim Sec 1=yes; 0=no
*50 SESCOA/RADIONICS SELECT
[0] 1=Sescoa; 0=Radionics
*51 DUAL REPORTING
[0]
1=yes; 0=no; If used with Spilt Reporting "1" option (1*34), alarms and alarm
restores go to both primary & secondary numbers, while all other reports go to
secondary only. If used with Split Reporting "2" option, alarms and alarm
restores go to both, open/close and test messages go to secondary only, while all
other reports go to primary.
*52 STANDARD/EXPANDED REPORT [0]
FOR PRIMARY Alarm Rstr Bypass Trbl Opn/Cls Low Bat
0=standard; 1=expanded; Note: Expanded overrides choices in 4+2 format.
*53 STANDARD/EXPANDED REPORT [0]
FOR SECONDARY Alarm Rstr Bypass Trbl Opn/Cls Low Bat
0=standard; 1=expanded; Note: Expanded overrides choices in 4+2 format.
*54 MAX. No. OF DIALLER ATTEMPTS
[8] Enter 1-8.
*55 TELEPHONE SYSTEM SELECT
|
[00]
00= SECURITEL
† options 01 01= Australia
*56 CONTACT ID DATA ON KEYPAD
[0]
BUS FOR ALT. COMM. Media 1= Yes
Reporting Instead Of Digicom 0= No
*57 CONTACT ID DATA ON KEYPAD
[0]
BUS FOR BACK-UP Alt. Comm. 1= Yes
Media Reporting If Digicom Fails 0= No
*58 SELECTION OF CONTACT ID
MESSAGE DATA ON KEYPAD Alarms Troubles Bypasses Open/ System Test
BUS FOR SUBSCRIBER ID#1 [0][0][0][0][0][0] Close Conditions Reports
1=Yes; 0=No