Vista 120 Training Guide 34
ZONE PROGRAMMING Cont.
• Press * to move to Partition
• Enter the Partition this Zone belongs to (1 –8).
• Press * to move to Report Code – Leave at “0 0” at this time
• Press * (3 times) to move to Input Type
• Enter the Type of Device being used for this Zone
INPUT TYPE
01 Hardwired Zone
03 Supervised RF (RF)
04 Unsupervised RF (UR)
05 Button RF (BR)
06 Serial Number Polling loop Device (SL)
07 Dip Switch Polling Loop Device
08 Right Loop of Dip Switch Device
• Press * to move to Zone Summary (See above diagram)
• Press * to return to move to “Enter Zone Number” display
• When you have finished programming all zones, Enter 000 as the next zone number & press “*” to quit
Zone Programming
• Then enter “1” (yes) to Exit Menu Mode
• Pressing “ # “ allows you to move backwards