Vista 120 Training Guide
23
VISTA 120 PROGRAMMING FORM
Some fields are programmed for each partition (shown as shaded fields). See the PARTITION-SPECIFIC section for programming these
fields. Standard default (*97) values are shown in brackets [ ], otherwise default = 0.
1*07 CHECK OR TROUBLE DISPLAY [0] 0=check; 1=trouble
1*08 SUPPRESS USE OF "ARMED"
[0]
LED ON KEYPADS 1= Yes
(For countries where Red is only for alarm) 0= No
1*09 SUPPRESS KEYPAD ARMING
[0]
STATUS INDICATIONS WHEN 1= Yes
SYSTEM IS ARMED 0= No
1*10 FIRST TO ALARM DISPLAY LOCK [0] 1=yes; 0=no
1*11 COMMON AREA 1 PARTITION [0] Enter the "common area 1" partition (1-8)
1*12 AFFECTS COMMON AREA 1 Partition-Specific
1*13 ARMS COMMON AREA 1 Partition-Specific
1*14 COMMON AREA 2 PARTITION [0] Enter the "common area 2" partition (1-8)
1*15 AFFECTS COMMON AREA 2 Partition-Specific
1*16 ARMS COMMON AREA 2 Partition-Specific
1*17 COMMON AREA 3 PARTITION [0] Enter the "common area 3" partition (1-8)
1*18 AFFECTS COMMON AREA 3 Partition-Specific
1*19 ARMS COMMON AREA 3 Partition-Specific
1*20 AUTOBYPASS FAULTED [0]
EXIT ROUTE ZONES 0=No, 1=Bypass E/E and Interior zones faulted after exit delay. (Australian
requirement)
1*21 EXIT DELAY RESET [0] 0=No; 1=Resets Exit Delay to 60 seconds after zone is closed.
1*22 CROSS-ZONING PAIR ONE | | | |
Enter 3-digit zone numbers to be linked so that both must fault within
a five minute period to cause an alarm.
1*23 CROSS-ZONING PAIR TWO | | | |
Enter 3-digit zone numbers to be linked so that both must fault within
a five minute period to cause an alarm.
1*24 CROSS-ZONING PAIR THREE | | | |
Enter 3-digit zone numbers to be linked so that both must fault within
a five minute period to cause an alarm.
1*25 CROSS-ZONING PAIR FOUR | | | |
Enter 3-digit zone numbers to be linked so that both must fault within
a five minute period to cause an alarm.
1*26 PANIC BUTTON OR SPEED KEY partition-specific
1*27 FIELD 1*31 TRANS. CHECK-IN [0]
SUPERVISION INTERVAL TO BE 1 = 1 hour (must be 1 hour for CENELEC compliance)
MULTIPLE OF 1 HOUR 0 = 2 hours
INSTEAD OF 2 HOURS