VISTA-15/VISTA-15CN Installation and Setup Guide
18–2
Cross Zoning - Zone List 04
Cross zone alarm verification is an option that must be set up using zone list 04, the cross
zone list, by selecting the desired cross zone numbers.
A cross zone is any combination of up to 10 zones of the following zone types:
• 01 - Entry/exit #1
• 02 - Entry/exit #2
• 03 - Perimeter
• 04 - Interior Follower
• 10 - Interior with Delay
The chosen zone numbers of the above types are to be entered into zone list 4 via field
✱
81. If
any of the zones fault in the armed state, the system waits to see if another zone in the zone
list faults within the cross zone list time entered in field
✱
85. If another zone faults, alarms
are sent out for both zones, the bell sounds, and the alarms are displayed on the keypad.
However, if another fault does not occur within the programmed cross zone time, a Trouble
report is sent to the Central Station and no message is displayed on the keypad until the
system is disarmed. Then a CHECK message is displayed on the keypad. This message can
be cleared by another
4-digit code
+ OFF sequence. The default for the cross zone timer is
30 seconds. Zone list 04 is empty by default.
U
L
This Zone List 04 is not to be used in UL installations.
NIGHT-STAY - Zone List 05
This mode only arms the Interior Follower and/or Interior with Delay zones programmed into
this zone list. All other interior zones are bypassed. The key sequence for arming in this
mode is:
4-digit code + 3 + 3.
The installer determines which zones are to be included in this
list. The interior zones (interior followers or interiors with delay) have the following
characteristics:
ARMING MODE INTERIOR ZONES INTERIOR ZONES IN ZONE LIST 05
STAY
Bypassed Does not apply
NIGHT-STAY
Bypassed Armed
NOTE:
When armed in this mode, the keypad displays
NIGHT-STAY
.