ADEMCO Security System VISTA-15CN Guia de preparacion Pagina 108

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 132
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 107
VISTA-15/VISTA-15CN Installation and Setup Guide
22–4
Relay/Powerline Carrier Device Activation
If relay outputs (via a
4204
or
4229
) or
Powerline Carrier devices
are used, two keypad
entries available to the user are included. They can manually activate or deactivate the
device(s) for starting or stopping some action, such as turning lights on or off, etc.
These keypad entries are:
[Security Code] + [#] + [7] + Device No. activates (starts) that device.
[Security Code] + [#] + [8] + Device No. deactivates (stops) that device.
4285/4286 VIP Module (if used)
Refer to the separate instructions supplied with the VIP module for information concerning
its operating procedures.
The VIP (phone module) cannot be used to add user codes in this system. User codes must be
added by using a wired keypad.
Exit Error Alarm Displays (if programmed)
A display of
CANCELED ALARM
or
CA
and a zone indication appears if an exit or
interior zone contained a fault during closing at the time the Exit Delay ended (e.g., exit
door left open), but the system was disarmed during the Entry Delay time. The alarm
sounder and keypad sound continuously, but stop when the system is disarmed. No
message is transmitted to the Central Station.
A display of EXIT ALARM or EA and a zone indication appears when the Exit Delay
ends if an exit or interior zone contained a fault during closing. The alarm sounder and
keypad sound continuously until the system is disarmed (or timeout occurs). An "Exit
Alarm" message is sent to the Central Station.
The EXIT ALARM display and zone indication also results if an alarm from an exit or
interior zone occurs within 2 minutes after the end of an Exit Delay.
In any of the above cases, use a second Off sequence (code plus OFF key) to clear the display.
Trouble Condition Displays
The word
CHECK
on the keypad's display, accompanied by a rapid beeping at the keypad,
indicates that there is a trouble condition in the system. Pressing any key silences the
audible warning sound. A Trouble report is sent to the Central Station, if programmed.
Instruct users to call for service immediately upon seeing any of the following messages. (See
Section 24: Troubleshooting Guide
also.)
CHECK and BATTERY Displays
A display of
CHECK
and one or more zone numbers
indicates that a problem exists with the
displayed zone(s) and requires attention in the disarmed state for the following conditions:
If control
senses
a high resistance in the loops on hardwired zones 2–6 it displays
CHECK and the affected zone number.
A display of
CHECK
and
09
indicates that communication between control and a zone
expander or wireless receiver is interrupted. Check the wiring and/or DIP switch settings
on the units.
If there are wireless sensors in the system, the
CHECK
condition may also be caused by
some change in the environment that prevents the receiver from receiving signals from a
particular sensor.
If control
senses
a short in the loops on hardwired zones 2–6 (If Hardwire Short
Detection is enabled in
30), it displays CHECK and the affected zone number. Unlike
the other CHECK conditions above, this Hardwired Short detection does not produce an
audible sound at the keypad.
Vista de pagina 107
1 2 ... 103 104 105 106 107 108 109 110 111 112 113 ... 131 132

Comentarios a estos manuales

Sin comentarios