VISTA-15/VISTA-15CN Installation and Setup Guide
16–4
If Serial or Loop
Numbers do not match
after activating the
transmitter
If the serial/loop number combination transmitted does not match
the serial number entered, a display similar to the one below
appears. If the loop number does not match, it is also displayed.
Keyd A022-4063
1
Rcvd A022-4064 1
If so, activate the transmitter's loop input or button one or more
times. If a match is still not obtained (i.e., summary display does
not appear), press the [#] key twice and enter the correct loop
input or, if correct, press the [#] key again and then enter the
correct serial number.
Zn ZT RC In:
L
10 03 10 RF:
1s
If the serial number transmitted matches the serial number
entered, the keypad beeps 3 times and a summary display
appears, showing that zone's programming. Note that an “s”
indicates that a transmitter’s serial number has been enrolled.
Press [
] to accept the zone information and display the
PROGRAM ALPHA? prompt.
PROGRAM ALPHA?
0 = NO 1 = YES 0
If you want to program descriptors for zones now, enter 1 (Yes) and
refer to Section 19: Alpha Descriptor Programming for
available descriptors.
ENTER ZN NUM.
(00 = QUIT) 11
If you entered 0 (No) above, the system returns you to the ENTER
ZN NUM. prompt for the next zone.
When all zones have been programmed, enter 00 to quit.
When you have finished programming all zones, test each zone using the
system’s TEST mode. Do not use the Transmitter ID Sniffer Mode for checking
wireless transmitting devices, as it only checks for transmission of one zone on
a particular transmitter,
not
the zones assigned to each additional loop.
NOTE: Following the successful enrollment of each wireless device, remove ONE of the
serial number labels from the device and affix it in the appropriate column on the
ENROLLED TRANSMITTERS worksheet of the Programming Form; then enter the other
information (zone number, zone type, loop number, etc.) relevant to that device. This
information would be useful if any troubleshooting is needed later on. The installer may want
to consider leaving this worksheet at the site (in the panel cabinet).
58 Expert Programming Mode Procedures
Enter the Program mode and follow the step-by-step instructions that follow.
NOTE: Before proceeding, you must program field
22 (RF System) and field
25 (Wired
Zone Expansion) as required.
SET TO CONFIRM?
0 = NO 1 = YES 0
Press
58. This display appears upon entry into this mode.
The default is 0 (No).
If you enter 1 (Yes), you are prompted to confirm each transmitter
after entering the serial and loop numbers (see “XMIT TO
CONFIRM” prompt below). We recommend that you confirm the
programming of every transmitter.