Section 5 - Wired Zone Expansion
5–3
Programming Wired Expansion Zones
Each zone must be programmed into the system using the
56 Zone Programming Mode or
58 Expert Programming Mode, which assigns characteristics that define the way the
system responds to faults on that zone. Refer to Section 14: Zone Response Type
Definitions and Section 16: Zone Programming for specific instructions on programming
wired expansion zones.
Checkout Procedure for Wired Expansion Zones
Whenever it becomes necessary to disconnect power in order to add a module or keypad, always
disconnect the battery first, then the AC transformer. After installation has been completed,
connect the AC transformer first, then the battery.
After
you
have completed installation and programming of all devices, check all expansion
zones in the security system as follows:
1.
Make certain that all devices and sensors connected to the wired expansion zones are not
in a faulted state. Doors and windows with contacts should be closed, PIRs should be
covered (use a cloth to mask them temporarily, if necessary).
2.
Plug in the AC transformer. With all zones intact (including hardwired zones), the alpha
keypad connected to the system should display:
✱✱✱✱
DISARMED
✱✱✱✱
READY TO ARM.
3.
If the following is displayed,
DISARMED
Press
to show faults
press [
]
to display the faulted zone(s). Restore any faulted zone(s) as necessary (also
make sure that you have connected a 1000 ohm
EOL resistor
across the terminals of
unused expansion zones on the
4219
or
4229
Module).
When the
READY TO ARM
message is displayed, you can proceed to the next step.
4.
Fault and restore every contact or sensor in each expansion zone individually to ensure
that it is being monitored by the system. Each time a zone is faulted, the keypad should
display the number of the faulted zone. When each zone is restored, the
READY TO
ARM
message should appear again.
You need to observe the keypad in each zone, as each zone is faulted and restored.
When the proper displays appear on the keypad(s), the wired expansion zones in the
system are functioning properly.
5.
Unplug the AC transformer.
A
CHECK 09
message on the display signifies one of two problems:
Data from the control is not reaching the zone expander module. Check the wiring and DIP
switch settings.
or
The tamper jumper is on in the Expansion Module and the Expansion Module cover is off.