Section 17 - Output Device Programming
17–5
2.
The second condition for turning on the indicator is triggering a
24-hour aux. zone (Zone Type 08). Therefore, program (ZT) as
08
. Press
[
✱
]
to continue.
3.
To stop the Device action and turn off the lamp, you do not
want to use a restore of any zone, so enter a
0
for Stop: Zn Lst
(ZL). Press
[
✱]
to continue.
4.
To stop the Device action and turn off the lamp, you do not
want to use a system operation or zone type, so enter a 0 for
Stop: Zn Typ. (ZT). Press
[
✱]
to continue.
NOTE:
A manual entry of
User Code + # + 8 + Device No
. (
1
in this example)
is used to turn the device off. Therefore, you do
not need to program a STOP event.
5.
The system displays a summary screen for the START
programming for device 01. Press
[
✱]
to continue.
6.
The system displays a summary screen for the STOP
programming for device 01. Press
[
✱]
to continue.
7.
The system displays the X10
?
prompt. Enter
1
for yes.
8.
The
ENTER DEVICE NO.
prompt for the next zone is
displayed.
Press
00
and then
[
✱]
to exit the
✱
80 mode.
Now use
✱
81 Zone List mode to program the 3 specific zones in Zone
List 01.
If you want to use zone type 12, 24-Hour Monitor, to activate a relay, all zones of that type must
be placed into a zone list and triggered by a “fault” event
. The same zone list must be
programmed for the “STOP” event. A restore of every faulted zone in that zone list is required to
deactivate the relay.