ASSIGN RESPONSE
TYPE FOR ZONE
17
ASSIGN RESPONSE
TYPES FOR ZONE
EZPANDER WIRING
SUPERVISION AND
FOR KEYPAD PANICS
DESIGNATE RIGHT
ZONE USAGE
ENTRY DELAY #1
W4
1[1[1 Zone17
2 [01[01
3 [01[0]
4 [01[01
5 [0][0] Zeroes to be entered
6 [01[01
7 [01[01
8 [01[0]
COMMENTS : Enter 2–digit
response types (see
Address *O2 for types) in field location 1 only
(enter 00 in fields 2-8).
*05
1 [01[01
2 [01[01
3 [01[01
Zeroes to be entered
4 [01[01
5 [ ] [ ] Short in Wiring to Zone Expander
(displays 97 or CALL SERVICE)
6 [ 1[ 1 1 & * Panic (displays 95)
7 [ 1[ ] 3 & # Panic (displays 96)
8 [ 1[ 1 * & # Panic (displays 99)
COMMENTS :
Enter response types (see Address *O2
for Vypes) in field locations 5–8 only (enter 00
in fields 1–4).
10 11 12 13 14 15 16
~6
[1[1[1[1[1[1[1
Zones 10-16
17
*(37
[1
Zone 17
CCE4MENTS:
All spaces
must be filled with O or 1
(1 if that zone is a right loop on a 4190WH
transponder or on a 4196 Quad PIR transponder).
When the 4208 is used as a Zone Expander, set all
zone number locations to O. Similarly, set the
zone number locations for 4194WH contact/
transponders,
4192 smoke detector base/
transponders, and 4275 PIRs to O, as well as left
loops on 4190WHs and the PIR portion of the 4196.
*08
NOT USED
*(’)9
[1[1
COMMENTS: Defines the time period between a fault
occurring in a zone to which Entry Delay #1 has
been assigned and the time when the alarm will
sound (UL 1023 Household Burglary usage permits a
maximum of 45 seconds).
Applies to the Interior,
Delay Zone type also.
Enter 00 -
15. Multiply by 15 seconds to determine
time delay (O 225 seconds available).
32