80 PROGRAMMING THE SYSTEM
- E. SYSTEM OPTIONS -
ENTRY DELAY #1
l 09
(01-15 times 15 seconds or 00 for no delay)
rj
mj
COMMENTS: Enter the entry delay time (multiply entry by 15
seconds for actual delay time), up to a maximum delay of 225
seconds (entry 15 times 15 seconds), for the zone assigned to Entry
Delay #l .
EXIT DELAY #l
‘10 rj
(01-15 times 15 seconds or 00 for no delay)
lolsl
COMMENTS: Enter the exit delay time (multiply entry by 15 seconds
for actual delay time), up to a maximum delay of 225 seconds. for the
zone assigned to Exit Delay #l .
ENTRY DELAY #2
‘11
(01-15 times 15 seconds or 00 for no delay)
171
lolsl
COMMENTS: Enter the entry delay time (multiply entry by 15
sewnds for actual delay time), up to a maximum delay of 225
seconds (entry 15 times 15 seconds), for the zone assigned to Entry
Delay
#2. Note thaf this delay must be longer than Entry Delay #l.
1 1 1
lolel
EXIT DELAY #2
‘12
(01-l 5 times 15 seconds or 00 for no delay)
COMMENTS: Enter the exit delay time (muflipfy entry by 15 seconds
for actual delay time), up to a maximum delay of 225 seconds, for the
.P
:
zone assigned to Exit Delay #k?.
Note that this
delay
must be bnger
._
than Exit
Delay #I.
ENTRY WARNING SOUND ‘67
(O/l 1
I
El
COMMENTS: Enter 0 for 3 short beeps, or 1 for slow beeps that
continue for the entire entry delay period.
ENABLE CONSOLE
ANNUNCIATION
DURING EXIT DELAY
(O/l 1
1’45
I
I
COMMENTS: Enter
1 if
beeps from the consoles during extt delay is
desired. Enter 0 for no console sound during exit delay.
.-..
ADEMCO’s VISTA
XM
SERIES TECENlCAL REFERENCE MANUAL