SYSTEbi CONFIGUBATION (ZONES)
2 5
GENERAL
INFORMATION
- C. 2-WIRE POLLING LOOP EXPANSION -
(ZONES 10 THROUGH 64)
To expand the system using
a
P-wire polling bop and remote point modules
(RPMs), a 4171XT-XM dialer board, and a 4152LMB loop module must be
installed, as de&bed in the ZONE EXPANSION MODULE section.
Any of the RPMs can be used, in any combination, to expand the system to a
maximum of 64 zones. For a complete list of available devices, see the
HARDWARE OVERVIEW section
The polling bop can be run in various ways, as shown. Choose the way that
best suits your needs, but make sure that polarity is correct throughout the
system. If polarity is reversed at any point, a Ioop short” will occur (displayed
as 197”). Calculate the total current required by completing the Polling Loop
Current Draw Worksheet found in the Summary of Connections section.
,
BASIC 9
HARDWIRED ZONES
Dlagmm 5A. ZONE EXPANSION USING RPM8
Diagram SB. VARIOUS POUING LOOP CONFlGURATlONS
Wire each of the RPMs In parallel to the P-wire polling loop, making sure no
more than the maximum allowable wire length is used per individual polling
bop run, as follows:
#22gauge@65o’max
#20 gauge @9w max
#18 gauge @lSOol max
#16 gauge @2400’ max
NOTE: Twisted pair recommended for all no-1 wire
NCIE.
IMPORTANT:
The maximum combined polling loop run is 4000’. If
uslng shielded wire, the maximum.is 2000’.
lf bnger wire
runs are needed, a 4197 Loop Extender module must m
be used.
ADEMCO’S VISTA
XM
SERIES TECENICAL REFERENCE
MANUAL