SYSTEM CONFIGURATION
POLLING LOOP
SMOKE DETECTORS
(4192S0, 4192SDT
OR 4192CP)
(PERIPHERALS)
,-,
Can be added to the g-wire Polling Loop via the 4152LME loop module, on
zones 10 through 84 (as programmed in fields ‘05, 1’02, 1’03, 1’04 and
l’OS).These detectors have a built-in RPM which is DIP switch
programmable. They are wired in parallel to the polling loop, and do not need>
auxiliary power or a separate reset switch. The polling bDp provides power
and reset signals to the
detectors,
as well as alarm and trouble signals from
the detectors.
4152LMB
POLLING
LOOP I
6.WIRE FOUlNO LOOP UIOKE DEl’SCTOR6
Diagram 22. P-WIRE POLLING LOOP SMOKE DETECTORS
ADVISORIES
1. The maximum polling kop runs are as follows:
l
#I22 gauge @ 650’ max.
l
#20 gauge @ 950’ max.
l
818 gauge @ 1500’ max.
l
#16 gauge @ 2400’ max.
IMPORTANT!:
The maximum combined polling loop run is 4000’. If
using shielded wire, the max. is 2000’.
2. Twisted pair is recommended lor all normal runs, but ii an intercom system
exists, or is being planned, you must keep the poking loop at least 8’
from the Intercom wiring, or use shielded wire. If not, you might
experience intercom interterence.
WIRELESS
Can be used on zones 48 through 55 as long as that zone is enabled for RF
SMOKE DETECTORS
usage in program fields 1’23 and/or 1’24, and are programmed as FIRE
(5706)
zones, type 09, in fields 1’03 an&or 1’04. These detectors have buiit-in
transmitters and are powered from a single 9 volt battery. A 4280 RF receiver
must be connected to the a-wire polling loop driven by the 4152LMB loop
module. These transmitter/detectors are DIP switch programmable and are
fully supervised for bw battery and check-in.
MODULE
+
4260 RF RECEIVER
*
e
(+I(-)
‘UP TO 0 #Nemo
B%iE
QQOO
oElFcTonscAN
BE USLD.
POLLING LOOP f-1
I
-A
a
POLLING LOOP (-1
63
5706
Diagram 23. RF SMOKE DETECTORS SMoKE
ADEMCO’s VISTA
XM
SERIES TECHNICAL REFERENCE MANUAL