26
SYSTEM CONFIGURATION (ZONES)
4197 LOOP EXTENDER
If longer polling bop wire runs are needed or more than MmA current is
being drawn on the polling loop, a 4197 Loop Extender Module must be
used. Diagram 6 shows typical connections. Note that power from a local
power supply is not approved for UL installation.
EnENDED POLLING LOOP
4197 POLLING EXTrNDER POWERED PROM PANEL
VISTA
CONTROL
NOTECONNECT TERMINALS 2
AND 3 AS SHOWN
POWER SUPPLY: (CONNECT TO AN UNINTER-
RUPTED 12Ot!. 6OHz POWER SOURCE THAT IS ON
INPUT POLLING LOOP
EXTENOED POLLING LOOP
n.
4197 POWERED PROM LOCAL POWER SUPPLY AND BARERY
Dlrgmm
6.4167 POWER CONNECTIONS
NOTE: Twisted pair recommended tor all normal wire runs.
CAUTfON: lf an intercom system is Being used, the polling loop wires must
be as far from the intercom wiring as possible (minimum 6’). If this spacing
cannot be achieved, shielded wire must be used. It this is not done,
interference on the Intercom system might occur. Also note that the
maximum total wire length supported is cut in half when shielded wire is used.
ADVISORY
The maximum allowable current draw on the polling loop is 64mA. Refer to
the Polling Loop Current Draw Worksheet (found in the SUMMARY OF
CONNECTIONS section) for current draws of various polling loop devices.-If
more than 64mA is being drawn, use of the 4197 provides another loop with
64mA available.
..--.
ADEMCO’s VISTA XM SERIES TRCHNICAL REFERENCE MANUAL