ZONE TYPE DEFINITIONS
TYPE 6
24 HOUR SILENT ALARM
This zone type is generally assigned to a zone containing a Hold-up or Panic
button that is designed to initiate an alarm report to the Central Station, but
which produces no visual displays or alarm sounds (ex: banks, jewelry
counters). Sensors assigned to this zone, when faulted, will only initiate a
programmed-communicator report.
TYPE 7
TYPE 8
TYPE 9 SUPERVISED FIRE
TYPE 10
24 HOUR AUDIBLE
This type also assigned to a zone containing a Panic button, but which will
initiate an audible alarm in addition to an alarm report to the Central Station
(ex: bedside panic). Faulting a zone of this type will initiate a kud audible
alarm externally and at the console, an LCD display, and a programmed
communicator report.
24 HOUR AUXILIARY
This type is assigned to a zone containing a button for use in personal
emergencies or to a zone containing monitoring devices such as water
sensors, temperature sensors, etc. Designed to initiate an alarm report to the
Central Station and only provides Console alarm sounds and alarm displays.
Fautttng a zone of this type will initiate a steady alarm sound at the console, an
ALARM display, and a programmed communicator report.
.*-..
Used for zones containing smoke detectors, heat detectors, pull stations,
etc. An open in this zone will initiite a trouble signal. A short in this zone will
initiate a fire alarm (pulsed external sounder and report to central station).
NOTE: Zone 1 can support up to three O-wire smoke detectors when
configured for use with a 13,000 ohm EOLR. Wired zones 1 through 8 (and
lo-94 if used) can support 4-wire smoke detectors when configured for
EOLR’s. but a manual power reset switch must be installed in order to reset
the smoke detectors after an alarm. Zones lo-94 can also use individually
identifiable a-wire polling loop smoke detectors (Zones 48-55 can use
wireless photoelectric smoke detectors). Zone 9 cannot be used for fire at
any time. Fire zones cannot be bypassed.
INTERIOR BURGLARY (DELAYED)
This type’ is similar to type 4. except that entry delay begins whenever
sensors in this zone are viotated, regardless of whether or not an entry/exit
delay zone was fautted first. This zone has the same delay times as entry/exit
#l and does not become active until after the exit delay time has elapsed.
Afterwards. if this zone is violated. entry time starts, and the system must be
disarmed before entry time elapses or an alarm will occur.