VISTA-128FBP/VISTA-250FBP Installation and Setup Guide
5-16
FIELD TITLE and DATA ENTRIES EXPLANATION
3*59
Enable Bell 2 & Auxiliary Relay
Chime Annunciation
0 = disable
1 = enable
This field has two entries, one for bell 2 and one for the auxiliary relay. If
enabled, the system produces chime annunciation on the output.
NOTE: Must be set to 0 if Bell 2 or Aux. Relay is used for Fire.
3*60
Bell 2 & Auxiliary Relay Timeout
Enter 01-15 multiplied by 2 minutes.
00 = no timeout.
This field has two entries, one for bell 2 and one for the auxiliary relay.
Defines the length of time the output and the keypads sounder will sound for
all audible alarms.
NOTE: Must be a minimum of 16 minutes for Commercial Burglary
installations and a minimum 6 minutes for UL Commercial Fire installations.
3*61
Auxiliary Relay Function
Selection
0 = trouble/supervisory
1 = alarm, silenced by User Code + OFF
2 = smoke detector reset
3 = battery save
4 = alarm, silenced by User Code + # + 67
Select the condition that will trigger the auxiliary relay.
NOTES:
Select 4 for applications requiring independent resetting of the relay.
Smoke detector reset triggers the relay momentarily (approximately 6
seconds) on the second User Code + OFF entry.
Battery save is used to disconnect power from non-critical loads 4 hours after
AC loss.
3*82
Burglary Features on Partition 1
Enable
0 = disable
1 = enable
If enabled, arming, test and chime modes can be used on partition 1.
NOTES:
These features are automatically enabled on all other partitions.
Must be set to 0 in Commercial Fire installations.
3*85
System Zone Bypass Inhibit
0 = prevent bypass
1 = allow only installer to bypass
2 = allow only installer and master codes to
bypass
Select which codes, if any, can bypass fire zones and systems zones.
NOTES:
This applies to fire zones programmed with zone types 9, 16, 17, and 18 and
system zones 970-977.
The bypassing can only be done from partition 1.